46
Location code
Description
12
Analog expander setup
14 Timers
setup
15 Display
options
16 Event/alarm
setpoints
17 Pulsing
setpoints
18
User assignable register map
20
Data log setup
21
Memory partitions setup
22
TOU energy registers setup
23
TOU demand registers setup
24
TOU daily profiles
25
TOU calendar
26
TOU calendar years
27
Relay control registers
28
User selectable options
31
DNP 3.0 class 0 map
32
DNP 3.0 options setup
33
DNP 3.0 events setup
34
DNP 3.0 event setpoints
35 Calibration
registers
36
Time zone information
Table 5-65 Event Effect Codes
Effect code
Description
0x6000
Clear energy registers
0x6100
Clear all demand registers
0x6101
Clear power demand registers
0x6100
Clear volt/ampere demand registers
0x6200
Clear TOU energy registers
0x6300
Clear TOU demand registers
0x6400
Clear all counters
0x6401-0x6404
Clear counters #1-#4
0x6500
Clear Min/Max log registers
0x6600
Clear Event log
0x6700-0x6707
Clear Data log #1-#8
0x6700
Clear all data logs
0xE100-0xE10F
Setpoint #1-#16 operated
0xE200-0xE20F
Setpoint #1-#16 released
0xF100-0xF10F
Setpoint #1-#16 cleared
0xF500 RTC
set
5.29 Data Log Registers
These registers allow you to circularly read consequent records from the event log file. Each data log file is
accessed via a separate register window. Reading from either register window always returns the next logged
record from the corresponding data log. All registers within one window must be read at once using a single
request. After reading a log window, the partition queue pointer is shifted forward until the end of the log file. After
the last record has been read, the file pointer is automatically restored to the beginning of the log file so that the
next read request will return the first (oldest) record. To point to an arbitrary record, use the data log partition
status/control registers (see Section 5.6).
Table 5-66 Data Log Window Locations
Data log number
Registers (see Table 5-67)
Data log #1
29696-29735
Data log #2
29736-29775
Data log #3
29776-29815
Data log #4
29816-29855
Data log #5
29856-29895
Data log #6
29896-29935
Data log #7
29936-29975
Data log #8
29976-30015
Reserved 30016-30335
TOU Monthly Profile Log. Energy Reg. #1