28
Memory Partition
Registers
(see Table 5-17)
Data log #3
28184-28191
Data log #4
28192-28199
Data log #5
28200-28207
Data log #6
28208-28215
Data log #7
28216-28223
Data log #8
28224-28231
Reserved 28232-28415
TOU Monthly Profile Log. Energy Reg. #1
28416-28423
TOU Monthly Profile Log. Energy Reg. #2
28424-28431
TOU Monthly Profile Log. Energy Reg. #3
28432-28439
TOU Monthly Profile Log. Energy Reg. #4
28440-28447
TOU Monthly Profile Log. Energy Reg. #5
28448-28455
TOU Monthly Profile Log. Energy Reg. #6
28456-28463
TOU Monthly Profile Log. Energy Reg. #7
28464-28471
TOU Monthly Profile Log. Energy Reg. #8
28472-28479
Reserved 28480-28543
TOU Monthly Profile Log. Max. Demand Reg. #1
28544-28551
TOU Monthly Profile Log. Max. Demand Reg. #2
28552-28559
TOU Monthly Profile Log. Max. Demand Reg. #3
28560-28567
Reserved 28568-28671
TOU Daily Profile Log. Energy Reg. #1
28672-28679
TOU Daily Profile Log. Energy Reg. #2
28680-28687
TOU Daily Profile Log. Energy Reg. #3
28688-28695
TOU Daily Profile Log. Energy Reg. #4
28696-28703
TOU Daily Profile Log. Energy Reg. #5
28704-28711
TOU Daily Profile Log. Energy Reg. #6
28712-28719
TOU Daily Profile Log. Energy Reg. #7
28720-28727
TOU Daily Profile Log. Energy Reg. #8
28728-28735
Reserved 28736-28799
TOU Daily Profile Log. Max. Demand Reg. #1
28800-28807
TOU Daily Profile Log. Max. Demand Reg. #2
28808-28815
TOU Daily Profile Log. Max. Demand Reg. #3
28816-28823
Reserved 28824-28927
If data log partition #7 is configured as a TOU monthly profile partition, registers 28216-28223 are mapped to
registers 28416-28423 for the first TOU monthly profile sub-partition allocated for TOU energy register #1, or for
the first following available TOU register if register #1 is not configured.
If data log partition #8 is configured as a TOU daily profile partition, registers 28224-28231 are mapped to
registers 28672-28679 for the first TOU daily profile sub-partition allocated for TOU energy register #1, or for the
first following available TOU register if register #1 is not configured.
Table 5-17 Log Partition’s Status/Control Window Registers
Parameter
Offset
Type
R/W
Range
Log partition status
+0
UINT16 R
Bit-mapped register:
bit 0 = 0 - non-wrap partition
= 1 - wrap-around partition
bit 4 = 1 - TOU monthly profile partition
bit 5 = 1 - TOU daily profile partition
bit 9 = 1 - reading after the end of file:
the read pointer has rolled over the end of a log file, that
is, the file is being re-read from the beginning. This bit is
cleared when the read pointer [+6] points to a new
record, or either command register [+6] or [+7] is
written.
The total number of records
logged in the partition/sub-
partition
+1
UINT16 R
0 to 65535. Returns the total number of logged records
available in the partition.
The number of the new records
never read before
+2
UINT16 R
0 to 65535. Returns the number of records from the first
new one never read before and until the end of the log file.