23
Parameter
Registers
Type
Timestamp 36982-36983
UINT32
Maximum real-time total values
Max. Total kW
37120-37121
INT32
Timestamp 37122-37123
UINT32
Max. Total kvar
37124-37125
INT32
Timestamp 37126-37127
UINT32
Total kVA
37128-37129
INT32
Timestamp 37130-37131
UINT32
Max. Total PF
37132-37133
INT32
Timestamp 37134-37135
UINT32
Maximum real-time auxiliary values
Reserved 37376-37379
INT32
Max. Neutral current
37380-37381
INT32
Timestamp 37382-37383
UINT32
Max. Frequency
37384-37385
INT32
Timestamp 37386-37387
UINT32
Maximum demands (M)
Max. volt demand L1/L12
37632-37633
INT32
Timestamp 37634-37635
UINT32
Max. volt demand L2/L23
37636-37637
INT32
Timestamp 37638-37639
UINT32
Max. volt demand L3/L31
37640-37641
INT32
Timestamp 37642-37643
UINT32
Max. ampere demand L1
37644-37645
INT32
Timestamp 37646-37647
UINT32
Max. ampere demand L2
37648-37649
INT32
Timestamp 37650-37651
UINT32
Max. ampere demand L3
37652-37653
INT32
Timestamp 37654-37657
UINT32
Reserved 37656-37667
INT32
Max. sliding window kW import demand
37668-37669
INT32
Timestamp 37670-37671
UINT32
Reserved 37672-37675
INT32
Max. sliding window kVA demand
37676-37677
INT32
Timestamp 37678-37679
UINT32
Reserved 37680-37691
INT32
Max. sliding window kW export demand
37692-37693
INT32
Timestamp 37694-37695
UINT32
TOU maximum demand register #1
Max. Demand Tariff #1 register
38144-38145
INT32
Timestamp 38146-38147
UINT32
Max. Demand Tariff #2 register
38148-38149
INT32
Timestamp 38150-38151
UINT32
...
...
Max. Demand Tariff #16 register
38204-38205
INT32
Timestamp 38206-38207
UINT32
TOU maximum demand register #2
Max. Demand Tariff #1 register
38400-38401
INT32
Timestamp 38402-38403
UINT32
Max. Demand Tariff #2 register
38404-38405
INT32
Timestamp 38406-38407
UINT32
...
...
Max. Demand Tariff #16 register
38460-38461
INT32
Timestamp 38462-38463
UINT32
TOU maximum demands register #3
Max. Demand Tariff #1 register
38656-38657
INT32
Timestamp 38658-38659
UINT32
Max. Demand Tariff #2 register
38650-38651
INT32
Timestamp 38652-38653
UINT32
...
...
Max. Demand Tariff #16 register
38716-38717
INT32
Timestamp 38718-38719
UINT32
1. Timestamp is given in local time in a UNIX-style time format: it represents the number of seconds since midnight (00:00:00),
January 1, 1970. The time is valid after January 1, 2000.