33
Output parameter
Point
Type
Unit
2
Scale
1
Con-
ID
Low
High
version
Real-time total values
Total kW
0x0F00 UINT16 0.001kW/1kW
-Pmax
Pmax
LIN3
Total kvar
0x0F01 UINT16 0.001kvar/1kvar -Pmax
Pmax
LIN3
Total kVA
0x0F02 UINT16 0.001kVA/1kVA 0
Pmax
LIN3
Total PF
4
0x0F03
UINT16
0.001
-1.000
1.000
LIN3
Total PF Lag
0x0F04 UINT16 0.001
0
1.000
LIN3
Total PF Lead
0x0F05 UINT16 0.001
0
1.000
LIN3
Real-time auxiliary values
Frequency
3
0x1002
UINT16
0.01Hz
0
100.00
3
LIN3
Average values per phase
Voltage L1/L12
5
0x1100
UINT16
0.1V/1V
0
Vmax
LIN3
Voltage L2/L23
5
0x1101
UINT16
0.1V/1V
0
Vmax
LIN3
Voltage L3/L31
5
0x1102
UINT16
0.1V/1V
0
Vmax
LIN3
Current L1
0x1103 UINT16 0.01A
0
Imax
LIN3
Current L2
0x1104 UINT16 0.01A
0
Imax
LIN3
Current L3
0x1105 UINT16 0.01A
0
Imax
LIN3
Average total values
Total kW
0x1400 UINT16 0.001kW/1kW
-Pmax
Pmax
LIN3
Total kvar
0x1401 UINT16 0.001kvar/1kvar -Pmax
Pmax
LIN3
Total kVA
0x1402 UINT16 0.001kVA/1kVA 0
Pmax
LIN3
Total PF
4
0x1403
UINT16
0.001
-1.000
1.000
LIN3
Total PF Lag
0x1404 UINT16 0.001
0
1.000
LIN3
Total PF Lead
0x1405 UINT16 0.001
0
1.000
LIN3
Average auxiliary values
Neutral current
0x1501 UINT16 0.01A
0
Imax
LIN3
Frequency
3
0x1502
UINT16
0.01Hz
0
100.00
3
LIN3
Present demands
kW import accumulated demand
0x160F UINT16 0.001kW/1kW 0
Pmax LIN3
kvar import accumulated demand 0x1610 UINT16 0.001kvar/1kvar 0
Pmax
LIN3
kVA accumulated demand
0x1611 UINT16 0.001kVA/1kVA 0
Pmax
LIN3
kW export accumulated demand
0x161A UINT16 0.001kW/1kW 0
Pmax LIN3
kvar export accumulated demand
0x161B UINT16 0.001kvar/1kvar 0
Pmax
LIN3
1
For parameter limits, see Note
1
to Table 5-1.
2
When using direct wiring (PT Ratio = 1), voltages are transmitted in 0.1 V units, currents in 0.01 A units, and powers in
0.001 kW/kvar/kVA units. For wiring via PTs (PT Ratio > 1), voltages are transmitted in 1V units, currents in 0.01 A units,
and powers in 1 kW/kvar/kVA units.
3
The actual frequency range is 45.00 to 65.00 Hz.
4
The output scale for signed (bi-directional) power factor is symmetrical with regard to
±
1.000 and is linear from -0 to
-1.000, and from 1.000 to +0 (note that -1.000
≡
+1.000). Negative power factor is output as [-1.000 minus measured
value], and non-negative power factor is output as [+1.000 minus measured value]. To define the entire range for power
factor from -0 to +0, the scales would be specified as -0/0. Because of the fact that negative zero may not be transmitted,
the value of -0.001 is used to specify the scale of -0, and both +0.001 and 0.000 are used to specify the scale of +0. To
define the range of -0 to 0, you must send -0.001/0.001 or -0.001/0.
5
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be
line-to-line voltages.
E
Available in the PM172E.
5.13 Digital Inputs Allocation Registers
Table 5-27 Digital Inputs Allocation Registers
Parameter
Register
Type
R/W
Range
Status inputs allocation mask
3292
UINT16 R
1
See Table 5-28
Pulse inputs allocation mask
3293
UINT16 R/W
See Table 5-28
Not used
3294
UINT16 R
1
Read as 0
External demand synchronization input mask
E
3295
UINT16 R/W
See Table 5-28
Time synchronization input mask
3296
UINT16 R/W
See Table 5-28
1
Writing to these locations is ignored. No error will occur.
E
Available in the PM172E.