7

Application Specifications

Please refer to Table for Application Specifications.

PARAMETER

VALUE

Response Time

1 second

Sensitivity

Refer Table No. 4

Table 3: Application Specifications

8

Installation Guidelines

While installing the instrument, please take care of the

following points:

1. The instrument should be installed in horizontal or ver-

tical position only.

Material Inlet Source

Figure 3: Proper Mounting Arrangement

2. Observe that when installed directly under the mate-

rial inlet source, a canopy called baffle of appropriate
strength and size should be welded right above the in-
strument as shown.

Material Inlet Source

Baffle

Figure 4: Coat-Endure with Baffle

3. To prevent the ingress of moisture and water seepage

in side mounting position, the cable entries should al-
ways point downwards.

Figure 5: Cable Gland Arrangement

4. Secure the cover of housing tightly. Tighten the cable

glands.

5. Make all electrical connections as instructed in the

manual. Don’t power on the device before verifying
the connections.

6. Weatherproofness of enclosure is guaranteed only if

the cover is in place glands adequately tightened.
Damage due to accidental entry of water can be
avoided if the instrument is installed in a rain shade.

7. If the ambient temperature is high, the instrument

should not be installed to receive direct sunlight. In
case such a position of shade is not available, a heat
shield should be fitted above the instrument especially
if the operating temperature lies between 60

C and

80

C.

9

Electrical Connections

Electrical connections for the instrument will change with

the models. Please refer to figure and the precautions
mentioned below before connecting the device.

Precautions for connecting Coat-Endure :

Power Supply Rating

Make sure the power supplied to the instrument is
within the specified range mentioned in Table 1.

Connect Earth

When supplying AC power, please make sure that the
grounding screw on the housing and the earth terminal
are all connected to the plant’s earth.

Power Supply Fluctuations & Noise

External noise or fluctuating power supplies could af-
fect performance and shorten the life of the instrument.
Use external line suppressors and fuse wires to con-
tain the risk of damage to the circuit.

AC Supply

DC Supply

L (Live)

N (Neutral)

90-265 V AC

18-55 V DC

+

ENTER

COAT-ENDURE

+

-

NC

C

NO

ON

DIP

1

2

3

4

1

2

COVER

UNCOVER

CALIBRATE

HI CALIBRATE

FS1

FS2

RELAY 1

RELAY 2

SENS

ITIVITY

1

2

3

4

5

6

Lo

+

-

OUT

R

L

(Available only in DC Power Supply)

L

N

E

Relay-1

PNP

(a) Electronics option SPDT Relay and PNP Output(SPN)

Figure 6: Electrical Connections

Sapcon Instruments Pvt.Ltd.

R

8

Summary of Contents for COAT-ENDURE

Page 1: ...COAT ENDURE Admittance Level Limit Switch INSTRUCTION MANUAL Version 3 0 ...

Page 2: ...ion Guidelines 8 9 Electrical Connections 8 10 Calibration 9 10 1 Calibration for Non conductive Material 9 10 2 Calibration for Conductive Material 9 11 Cover Delay 10 12 Uncover Delay 10 13 Sensitivity 11 14 Failsafe 12 15 Display Indications 12 15 1 STATUS LED 12 15 2 LED Bar Display 12 16 Factory Reset 12 17 Output Options 13 18 Error Indication 13 19 Customer Support 13 20 Product Selection O...

Page 3: ...bration Switch Position 10 14 Setting Calibration 10 15 Saving Calibration 10 16 DIP Switch 10 17 Cover Switch Position 10 18 Setting Cover Delay 10 19 Saving Cover Delay 10 20 Uncover Switch Position 11 21 Setting Uncover Delay 11 22 Saving Uncover Delay 11 23 Sensitivity Bar Display 11 24 Setting Sensitivity 11 25 Setting Sensitivity 11 26 Failsafe High 12 27 Failsafe Low 12 28 LED Indication on...

Page 4: ...dure User Manual Datasheet V 3 0 List of Tables 1 Electrical Specifications 7 2 Mechanical Specifications 7 3 Application Specifications 8 4 Sensitivity 12 5 Error Indication 14 Sapcon Instruments Pvt Ltd R 4 ...

Page 5: ...pcon Instruments Pvt Ltd The images shown in this manual may differ from the actual instrument housing in terms of dimensions color and design Please refer to GA drawings for dimensional details Values of performance described in this manual were obtained under ideal testing conditions Hence they may differ under industrial environment and settings General Instructions Instrument shouldn t block t...

Page 6: ... the device is able to identify the differential coating between the sense and the shield by measuring their individual ca pacitances As the coating immunity is controlled by the on board microcontroller the extent of coating immunity can be set easily Figure 2 Description of Parts 3 Features Universal power supply of 18 55 V DC and 90 265 V AC on the same terminal Compact and customizable probe s...

Page 7: ...ed Delays Relay Rating 6 Amps at 230V AC Table 1 Electrical Specifications 6 Mechanical Specifications Please refer to Table 2 for Mechanical Specifications PARAMETER VALUE Housing SCUTE Pressure die cast aluminium weatherproof Rating IP 68 FP2C Cast aluminium weatherproof flameproof powder coated suitable for Gas Groups IIA IIB IIC as per IS 2148 Electrical Connector 2 x 1 2 BSP NPT PG 13 5 Opera...

Page 8: ...f the instrument is installed in a rain shade 7 If the ambient temperature is high the instrument should not be installed to receive direct sunlight In case such a position of shade is not available a heat shield should be fitted above the instrument especially if the operating temperature lies between 60 C and 80 C 9 Electrical Connections Electrical connections for the instrument will change wit...

Page 9: ...LIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 CLOSE Lo Figure 9 Calibration Switch Position ENTER COAT ENDURE ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 CLOSE Lo Figure 10 Setting Calibration Press and hold ENTER key The STATUS LED for RE LAY 1 will glow in RED color Release the ENTER key and set the CALIBRATE switch b...

Page 10: ...as shown in Figure 17 3 Press ENTER The STATUS LED for RELAY 1 starts blinking Blink the STATUS LED according to value of cover delay ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 CLOSE Figure 16 DIP Switch ENTER COAT ENDURE ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 CLOSE Lo Figure 17 Cover Switch Position ENTER COAT ENDURE ON...

Page 11: ...djusted de pending on the dielectric constant of the application media Coat Endure has a LED bar display which helps in visual izing the desired sensitivity level The device ships with a default sensitivity level of 3 Traverse the following steps to set the sensitivity of Coat Endure 1 Set the UNCOVER and CALIBRATE switch to CLOSE position ENTER COAT ENDURE ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE H...

Page 12: ...e STATUS LED sections indicate switching status for RELAY 1 and RELAY 2 ENTER COAT ENDURE ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 CLOSE Lo Figure 27 Failsafe Low ENTER COAT ENDURE NC C NO ON DIP 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 Lo OUT L N E Relay 1 PNP STATUS LED Figure 28 LE...

Page 13: ...On error the status LED starts blinking RED and GREEN alternately at a faster rate Normal LED blinks are always at the rate of 1 blink per second in either RED or GREEN color In some cases a GREEN or a RED blinking could ENTER COAT ENDURE ON 3 4 5 6 1 2 COVER UNCOVER CALIBRATE HI CALIBRATE FS1 FS2 RELAY 1 RELAY 2 SENSITIVITY 1 2 3 4 5 6 CLOSE Lo Figure 33 Single Point Switching without Material in...

Page 14: ...he probe connector Clean the connector and use the instrument GREEN Blinking Probe Open Remove the electronic insert from the housing and check the cable connections of the probe 3 Times GREEN Blinking and 1 Red Blink Illegal Key Combination Switch all DIP switches to open position Use only legal combina tion of keys 3 Times RED Blinking and 1 GREEN Blink Circuit Error Contact the Customer Support...

Page 15: ...o 35V DC Power Supply Depend on Housing U Universal 18 to 55V DC and 90 to 265V at 50Hz AC on same terminals Insulation Type P Part PTFE F Full PTFE Mounting MB5S4 Screwed Thread BSP 1 2 SS 304 MB5S6 Screwed Thread BSP 1 2 SS 316 MN5S4 Screwed Thread NPT 1 2 SS 304 MN5S6 Screwed Thread NPT 1 2 SS 316 MB75S4 Screwed Thread BSP 3 4 SS 304 MB75S6 Screwed Thread BSP 3 4 SS 316 MN75S4 Screwed Thread NP...

Page 16: ...h SS 316 Only for Probe Length 150mm S40S4 40mm Length SS 304 Only for Probe Length 151mm S40S6 40mm Length SS 316 Only for Probe Length 151mm Shield Depends on Sense SH11S4 11mm Length SS 304 Only with S20S4 SH11S6 11mm Length SS 316 Only with S20S6 SH20S4 20mm Length SS 304 Only with S40S4 SH20S6 20mm Length SS 316 Only with S40S6 Grounding Length Depends on Probe Length 85mm or 0 85H GS4 SS 304...

Reviews: