26
7-1-4. Additional Materials Required for Installation
(1)
(2)
(3)
(4)
(5)
Refrigeration (armored) tape
Insulated staples or clamps for connecting wire
(See local codes)
Putty
Refrigeration lubricant
Clamps or saddles to secure refrigerant tubing
30
30
Limit of Elevation
Difference (H1, H2)
(m)
Model
Max. Allowable Tubing
Length
(m)
Table 2
243
303
7.5
7.5
DO:
install the unit within the maximum elevation difference
(H1, H2) above or below the outdoor unit and within the
maximum allowable tubing length from the outdoor unit
to the door unit as detailed in table2 and Fig2a and Fig2b.
install the inter-unit cable more than 1 meter away
from any antenna or power lines or connecting wires
used for television, radio, telephone, security
system, or intercom. Electrical noise from any of
these sources may affect operation.
select a location where tubing and drain hose have the
shortest run to the outside. (Fig 1a)
select a location that will hold the weight of the unit.
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best)
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig 1b)
AVOID:
places where large amounts of oil mist exist.
areas where leakage of flammable gas may be expected.
nearby heat sources that may affect performance of the
unit.
direct sunlight.
7-2. Installation Site Selection
7-2-1. Indoor Unit
To prevent abnormal heat genera-
tion and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or sur-
rounding the air conditioner in a
way that may block air flow.
WARNING
This outdoor unit requires no refrigerant
charge up to the maximum limit for the
maximum allowable tubing length of 7.5m
(243, 303). Therefore, the refrigerant
needs to be added on-site.
NOTE
INDOOR
UNIT
H1
OUTDOOR
UNIT
Fig. 2a
INDOOR
UNIT
H2
OUTDOOR
UNIT
Fig. 2b
Fig. 1a
Indoor unit
Drain hose
Outside drainage
Fig. 1b
15cm
min.
15cm
min.
15 cm min.
Front View