For indoor unit type
(SAP-KMRV76EH, KMRV96EH, KMRV126EH)
(SAP-KRV96EHDS)
(SAP-KRV186EH, KRV246EH)
After turning on the power of the air conditioner, use the remote
controller and follow the steps below to conduct the test run.
(1) Set the remote controller in Test Run mode. (Fig. 59a-1)
a)Press and hold the QUIET button and the 1HR. TIMER button.
b)Then press and hold the ACL (Reset) button with a pointed
object such as the tip of a pen. After 5 seconds, release the
ACL button first.
c) Then release the QUIET and 1HR. TIMER buttons.
d)
appears and “oP-1” blinking in the remote controller clock
display area. (Fig. 59b-1)
(2) Start Cooling mode test run by pressing the ON/OFF operation
button of the remote controller. (Fig. 59a-1)
• This starts the fan producing uncooled forced air with the 3 indi-
cator lamps (OPERATION lamp, TIMER lamp, and LED CLEAN
lamp) on the main unit blinking. (Fig. 59c-1 or 59c-2)
• After 3 minutes, the system shifts into cooling operation, and
cool air will start to be felt. Cooling mode test run is unaffected
by the room temperature.
(3) Press the ON/OFF operation button of the remote controller again
to stop the test run. (Fig. 59a-1)
(4) Finally press the ACL (Reset) button of the remote controller to
release it from Test Run mode to return to normal mode.
(Fig. 59a-1)
• “
” and “oP-1” will disappear from the remote controller clock
display area.
After the test run is completed, be sure to press the ACL (Reset)
button to return to normal mode. The air conditioner will not operate
correctly if this is not done.
IMPORTANT