12
WM – 700699
6. ELECTRICAL DATA
●
Electrical Characteristics
CM3212 / KMS0712
×
1
Remarks:
Rating conditions are: Outside air temperature 95°F DB/75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Performance at
Indoor Unit
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Fan Motor
Compressor
Rating Conditions
A
0.15 / 0.14
0.62 / 0.56
2.53 / 2.80
3.3 / 3.5
W
34 / 28
140 / 126
576 / 566
750 / 720
Locked-Rotor Amperes
A
0.19 / 0.18
1.95 / 1.77
22
—
CM3212 / KMS1812
×
1
Remarks:
Rating conditions are: Outside air temperature 95°F DB/75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Performance at
Indoor Unit
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Fan Motor
Compressor
Rating Conditions
A
0.4 / 0.4
1.45 / 1.42
7.05 / 7.68
8.9 / 9.5
W
90 / 80
330 / 290
1,580 / 1,580
2,000 / 1,950
Locked-Rotor Amperes
A
0.45 / 0.40
1.95 / 1.77
54
—
CM3212 / KMS7012
×
2
Remarks:
Rating conditions are: Outside air temperature 95°F DB/75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Performance at
Indoor Units
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Fan Motor
Compressor
Rating Conditions
A
0.30 / 0.28
1.45 / 1.42
4.95 / 5.5
6.7 / 7.2
W
68 / 56
330 / 290
1,142 / 1,144
1,540 / 1,490
Locked-Rotor Amperes
A
(0.19 / 0.18)
×
2
1.95 / 1.77
22
×
2
—
92-131 S/M (Basic) 2/21/01 4:49 PM Page 12