I - 110
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions
: Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature
95
°
F DB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature 115
°
F DB
Heating:
Rating Conditions
: Indoor Air Temperature
70
°
F DB / 60
°
F WB
Outdoor Air Temperature
47
°
F DB / 43
°
F WB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / —
°
F WB
Outdoor Air Temperature
45
°
F DB / 35
°
F WB
Indoor model: TH2442 / Outdoor model: CH2442
●
Cooling
●
Heating
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.4 - 0.4
0.9 - 0.9
10.4 - 11.6
11.7 - 12.9
kW
0.08 - 0.07
0.18 - 0.17
2.29 - 2.26
2.55 - 2.50
Full load conditions
A
0.4 - 0.4
0.9 - 0.9
11.4 - 11.8
12.7 - 13.1
kW
0.08 - 0.07
0.18 - 0.17
2.55 - 2.44
2.81 - 2.68
Starting amperes
A
1 - 1
1 - 1
66 - 60
68 - 62
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.4 - 0.4
0.9 - 0.9
9.4 - 10.0
10.7 - 11.3
kW
0.08 - 0.07
0.18 - 0.17
2.09 - 2.04
2.35 - 2.28
Full load conditions
A
0.4 - 0.4
0.9 - 0.9
11.0 - 11.7
12.3 - 13.0
kW
0.08 - 0.07
0.18 - 0.17
2.45 - 2.42
2.71 - 2.66
Starting amperes
A
1 - 1
1 - 1
66 - 60
68 - 62