SM830044
– 56 –
4
4. Service procedures
0874_X_S
Is drainage prevented from
flowing ?
• Check drain hose.
YES
• Check float switch (FS).
NO
b)
Check compressor motor thermal protector (49C)
0628_X_S
• Check voltage between
terminals No.2 and No.4 at
terminal plate.
• Check P.C.B. Ass’y.
No voltage appears.
P.C.B. Ass’y is defective.
D.
Check indoor unit P.C.B.
E.
Check float switch.
0626_X_S
Is temperature of compressor
abnormally high ?
Refrigerant gas shortage.
YES
NO
Compressor is defective.
Charge refrigerant gas.
• Check compressor motor
thermal protector. (49C)
0627_X_S
• Check compressor motor
magnetic contactor.
(52C)
(Only outdoor fan does not run.)
Summary of Contents for 854 012 22
Page 6: ... 6 SM830044 ...
Page 30: ... 30 SM830044 2 2 Processes and functions ...