– 11 –
SM830044
1
1. Specifications
1. Specifications
1. Specifications
MODEL No.
Indoor Unit
SPW-D253G56
Outdoor Unit
SPW-C253G8, SPW-C253G8/M
POWER SOURCE
380 - 400 - 415 V / 3 N / 50 Hz
PERFORMANCE
Cooling
Capacity
kW
7.3
BTU / h
25,000
Air circulation (Hi/Me/Lo)
m3 / h
1,380/1,320/1,260
Moisture removal(High)
Liters/h
3.1
External static pressure(High)
mmAq(Pa)
19(186):at shipment
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Available voltage range
V
342 - 456
Running amperes*
A
5.2
5.2
5.1
Max. running amperes**
A
6.5
6.3
6.2
Power input
kW
3.15
3.17
3.19
Power factor
%
92
88
87
C.O.P
W / W
2.32
2.3
2.29
Max. starting amperes
A
28
30
31
FEATURES
Controls
Microprocessor
Timer
ON / OFF 12-hours
Fan speed (Indoor)
3 and Automatic control
Airflow direction (Indoor)
-
Air filter
Field supply
Remote controller (Accessory)
RCS-U251G
Refrigerant control
Capillary tube
Drain pump (drain connection)
No (25A,OD32mm)
Compressor
Rotary
Operation sound
Indoor - Hi/Me/Lo
dB - A
44 / 43 / 42
Outdoor - Hi
dB - A
53
REFRIGERANT TUBING
Limit of tubing length
m (ft.)
40 (131)
Limit of tubing length at shipment
m (ft.)
15 (49)
Limit of elevation difference
m (ft.)
Outdoor unit is higher than indoor unit: 40 (131)
between the two units
Outdoor unit is lower than indoor unit: 25 (82)
Refrigerant tube
Narrow tube
mm (in)
6.35 (1 / 4)
outer diameter
Wide tube
mm (in)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
R22 - 2.4
DIMENSIONS & WEIGHT
Indoor unit
Outdoor unit
Unit dimensions
Height
mm (in)
420 (16-17/32)
735 (28-30/32)
Width
mm (in)
1,065 (41-30/32)
940 (37)
Depth
mm (in)
620 (24-13/32)
340 (13-12/32)
Package dimensions
Height
mm (in) 513 (20-6/32)
826 (32-17/32)
Width
mm (in)
1,148 (45-6/32)
1,016 (40)
Depth
mm (in)
713 (28-2/32)
416 (16-12/32)
Net weight
kg (lb) 47 (104)
68 (150)
Shipping weight
kg (lb) 61 (134)
74 (163)
Shipping volume
m
3
(Cu. ft.)
0.42 (14.8)
0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions(*) :
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions(**) Indoor air temperature 35
°
CDB / 25
°
C WB, Outdoor air temperature 50
°
C DB
1-1 Unit Specifications
Cooling :
Rating conditions(*) :
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions(**) : Indoor air temperature 35
°
C DB / 25
°
C WB, Outdoor air temperature 50
°
C DB
Summary of Contents for 854 012 22
Page 6: ... 6 SM830044 ...
Page 30: ... 30 SM830044 2 2 Processes and functions ...