5
Two beeps are heard. The setting is saved and the UPS returns
to normal operation.
§
§
3
3
.
.
2
2
S
S
e
e
t
t
t
t
i
i
n
n
g
g
O
O
u
u
t
t
p
p
u
u
t
t
V
V
o
o
l
l
t
t
a
a
g
g
e
e
①
Check that the UPS is in the following condition.
②
Press and hold
for 3 or 4 seconds. Then release it when two beeps are heard.
③
Quickly press
several times (within 3 seconds) to set the 5 LEDs surrounded by in the figure
below to a blinking pattern such as the one in the figure.
④
Quickly press
several times (for no more than 3 seconds) to switch to the setting value LED
blinking pattern to select for the 4 LEDs surrounded by
in the figure below.
⑤
Press and hold
for 3 or 4 seconds.
Then release it when two beeps are heard.
⑥
Restart the UPS.
LEDs that blink when the “120 V” or “240V” setting is
selected.
100V Model
Setting
Setting LED
Description
100V
●
○
○
○
110V
○
●
○
○
115V
●
●
○
○
120V
○
○
●
○
The default setting varies depending
on the UPS model. Check your UPS
model and see §12.2 “Setup Menu
List” in the
E11A Instruction Manual.
200V Model
Setting
Setting LED
Description
200V
●
○
○
○
220V
○
●
○
○
230V
●
●
○
○
240V
○
○
●
○
208V
●
○
●
○
The default setting varies depending
on the UPS model. Check your UPS
model and see §12.2 “Setup Menu
List” in the
E11A Instruction Manual.
The rated output voltage is the same as the rated input
voltage. Check the input voltage to select the output voltage.
Set the output voltage. Select the output
voltage according to your using environment.
MAIN SW on the back panel set to “ON” *1
The “Green INV.ON/STAND BY” and
the “Green OUTPUT are not blinking. *2
*1. Operation is possible regardless of whether
is ON or OFF.
*2. If these LEDs are blinking, Forced Bypass switch
may be set to “Bypass”. Set this switch to “Inverter”,
and restart the UPS.
Tip
The UPS switches to the user setting mode.
Buzzer sounds : 2 beeps
:
Either BATT.LOW or 25
blinks,
or both
BATT.LOW and 25
blink.
:
INPUT blinks.
:
LED is off.
:
LED is blinking.
If you change other menus, shut down the UPS after changing all
settings. Then restart the UPS. Be sure to power off the load devices
before shutting down the UPS.
Note
The blinking pattern changes each time you press
or
.
If you miss the LED blinking pattern you want to select, continue pressing
the button repeatedly until the LED blinking pattern is redisplayed.
Tip
Hold for 3 or 4 sec.
until 2 beeps.
Press
Press
Hold for 3 or 4 sec.
until 2 beeps.