background image

 

 

 

26 

Two beeps are heard. The setting is saved and the UPS returns 

to normal operation. 

 

§

§

3

3

.

.

2

2

3

3

 

 

S

S

e

e

t

t

t

t

i

i

n

n

g

g

 

 

O

O

u

u

t

t

l

l

e

e

t

t

 

 

B

B

o

o

x

x

 

 

O

O

U

U

T

T

P

P

U

U

T

T

1

1

 

 

O

O

F

F

F

F

 

 

D

D

e

e

l

l

a

a

y

y

 

 

T

T

i

i

m

m

e

e

 

 

 

 

 

 

When using the supplied power management software, you cannot set this menu on the control panel of the UPS.   

Set this menu using the power management software. Refer to the User Guide of the power management software. 

 

 

Check that the UPS is in the following condition. 

 

 

 

 

 
 

 

Press and hold 

  for 3 or 4 seconds. Then release it when two beeps are heard. 

 

 
 

 

 

 

 

 
 

 

 

 

Quickly press 

  (within 3 seconds) several times to set the 5 LEDs surrounded by              in the figure 

below to a blinking pattern such as the one in the figure. 

 

 

 

 

 

 

 
 

 

 

 

 

 

Quickly press 

  (within 3 seconds) several times to switch to the setting value LED blinking pattern 

to select for the 4 LEDs surrounded by 

  in the figure below. 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

Press and hold 

  for 3 or 4 seconds.   

Then release it when two beeps are heard. 

 

 
 

 

 

 

LEDs that blink when the “5 seconds” setting is selected.

 

 

 
 

 

Setting

 

Setting LED

Description

 

0

 seconds

● ○ ○ ○

5

 seconds

○ ● ○ ○

30

 seconds

● ● ○ ○

1 minute

○ ○ ● ○

5 minutes

● ○ ● ○

10 minutes

○ ● ● ○

OUTPUT1 OFF occurs after 

passage of the specified time 
following a UPS OFF operation.

 

The specified OFF delay time is enabled only when you specify 

“Enabled” in §3.20 “Enabling and Disabling Output line 

Control”. If, after specifying and confirming “Enabled”, you then 

change the setting to “Disabled” and restart the UPS, the OFF 

delay time set with this menu item returns to the default value 

of “0 seconds”.

 

Default

setting

Press

 

The blinking pattern changes each time you press 

  or 

If you miss the LED blinking pattern you want to select, continue pressing 

the button repeatedly until the LED blinking pattern is redisplayed.

 

Tip

Press

 

If you want to perform output line control, set the outlet box OUTPUT1 OFF delay time. 

The specified OFF delay time is enabled only when §3.20 is set to “Enabled”.  

This menu is available for 011 and 012 model.

When using the power management software, 

the LEDs may blink as shown in the left figure. 

You cannot set on the control panel of the UPS. 

Change the setting using the power management 

software.  

  MAIN SW    on the back panel set to “ON” *1 

 

The “Green INV.ON/STAND BY” and 

the “Green OUTPUT are not blinking. *2

 

*1. Operation is possible regardless of whether 

 

is ON or OFF. 

*2. If these LEDs are blinking,    Forced Bypass  switch 

may be set to “Bypass”. Set this switch to “Inverter”, 

and restart the UPS. 

 

Tip

The UPS switches to the user setting mode.

 

 

Buzzer sounds : 2 beeps

 

 

Either BATT.LOW or 25 

blinks,  

or both

 BATT.LOW and 25 

blink.

 

 

INPUT blinks. 

LED is off. 

LED is blinking.

 

Hold for 3 or 4 sec. 

until 2 beeps. 

Hold for 3 or 4 sec. 

until 2 beeps. 

Summary of Contents for SANUPS E11A Series

Page 1: ...User Settings Guide Uninterruptible Power Supply M0009096B ...

Page 2: ...S Operation Upon Power Recovery 10 3 8 Setting Buzzer Sound 11 3 9 Setting UPS Shutdown Operation 12 3 10 Setting Overload Recovery Operation 13 3 11 Setting UPS Operation at OFF 14 3 12 Setting Low Battery Voltage Warning Timing 15 3 13 Setting Battery Backup Time 16 3 14 Setting Battery Type 17 3 15 Setting Battery Test Schedule 18 3 16 Resetting Battery Information 19 3 17 Enabling and Disablin...

Page 3: ... Setting Remarks Auto Double Conversion 1 4 3 1 UPS operation mode Economy 100V 200V 110V 220V 115V 230V 120V 240V 2 5 3 2 Output voltage RESTART 208V See remarks Select the menu by the blinking pattern of 5 LEDs The blinking pattern changes each time you press Pressing this button repeatedly cycles through the LED blinking patterns For the menus indicated by RESTART in this column restart of the ...

Page 4: ...Set the operation for switch to stop the UPS power supply Auto return Auto recovery when a certain period of time has elapsed 10 13 3 10 Overload recovery operation Bypass Fixed as bypass power supply on overload Set the UPS operation after switching to the bypass power supply because of overload OFF The UPS stays off 11 14 3 11 UPS operation at OFF RESTART Bypass Bypass power supply Specify the U...

Page 5: ...3 24 Outlet box OUTPUT2 OFF delay time 5 minutes Set the OFF delay times for the OUTPUT1 and OUTPUT2 terminals of the outlet box The delay times are not enabled unless item 3 20 Enabling and Disabling Output line Control is set to Enabled Until batteries exhausted 0 seconds 30 seconds 1 minute 3 minutes 25 28 3 25 Outlet box OUTPUT1 power outage output time 5 minutes Until batteries exhausted 0 se...

Page 6: ...e according to the condition of the input power or the load devices UPS operation mode Economy mode when power conditions are good UPS supplies its power to the load devices Double Conversion mode when power conditions fluctuate UPS converts to the stable power and supplies to the load devices Active Filter Mode when load power fluctuates suppresses high frequencies generated by the load devices a...

Page 7: ...lt setting varies depending on the UPS model Check your UPS model and see 12 2 Setup Menu List in the E11A Instruction Manual The rated output voltage is the same as the rated input voltage Check the input voltage to select the output voltage Set the output voltage Select the output voltage according to your using environment MAIN SW on the back panel set to ON 1 The Green INV ON STAND BY and the ...

Page 8: ...economy mode and auto mode operation 1 Operation is possible regardless of whether is ON or OFF 2 If these LEDs are blinking Forced Bypass switch may be set to Bypass Set this switch to Inverter and restart the UPS Tip The UPS switches to the user setting mode Buzzer sounds 2 beeps Either BATT LOW or 25 blinks or both BATT LOW and 25 blink INPUT blinks LED is off LED is blinking LEDs that blink wh...

Page 9: ...he UPS by the procedures of UPS Battery Power Startup in 11 1 UPS Startup in the E11A Instruction Manual LEDs that blink when the 60Hz setting is selected Setting Setting LED Description 50 Hz 60 Hz The default setting varies depending on the UPS model Check your UPS model and see 12 2 Setup Menu List in the E11A Instruction Manual Set the output frequency when starting the UPS from battery power ...

Page 10: ...n using the following functions The power management software LAN Interface card UPS remote ON and One touch system shutdown by remote switch Serial Login Shutdown by serial login Do not use this setting 1 When using 001 model do not use this setting Set the interface mode when using external interface connector Default setting The blinking pattern changes each time you press or If you miss the LE...

Page 11: ... Description 9600 9600 bps 4800 4800 bps 2400 2400 bps Select 9600bps when using the LAN interface card Set the serial baud rate when a workstation PC or optional LAN Interface card is connected Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redispl...

Page 12: ...tically when battery charge reaches 30 after the utility power recovers 50 The UPS restarts automatically when battery charge reaches 50 after the utility power recovers 80 The UPS restarts automatically when battery charge reaches 80 after the utility power recovers After changing the setting shut down the UPS then restart the UPS Be sure to power off the load devices before shutting down the UPS...

Page 13: ...ery test battery test result error and emit key click sounds Pattern 1 Emit beeps at serious failure battery warning and emit key click sounds Pattern 2 Emit beeps at alarm and emit key click sounds OFF Emit key click sounds only The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking...

Page 14: ... button when the buzzer starts beeping Pressing for at least 3 seconds while the buzzer is beeping shuts down the UPS This setting is the function to prevent shutdown of the UPS by an accidental operation This setting is available for shutdown operation only Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing...

Page 15: ...tches to UPS power supply operation every 2 5 seconds and switches back to bypass power supply if the overload condition still persists This cycle is repeated 2 If the utility power voltage is low and the load current is below the overload detection threshold when the UPS switches to bypass power supply the UPS may continue to switch between UPS power supply and bypass power supply Default setting...

Page 16: ...y the UPS supplies the bypass power Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redisplayed Tip Specify the UPS power supply conditions when the UPS is stopped by the procedure in 11 2 UPS Shutdown Daily in the E11A Instruction Manual MAIN SW on ...

Page 17: ...ed when remaining battery duration is 2 minutes 3 minutes Warning is emitted when remaining battery duration is 3 minutes The buzzer does not sound when OFF or Pattern 2 is selected as the setting value in 3 8 Setting Buzzer Sound If you are using the power management software the above setting is disabled and the warning is emitted at the timing set for performing UPS shutdown in the power manage...

Page 18: ...external battery box When the 20minutes battery box is connected 20 minutes must be selected Even if 40 minutes is selected the actual backup time cannot be extended to 40 minutes The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redisplayed Tip Default setting Set th...

Page 19: ... service life cannot be extended to 10 years Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redisplayed Tip Set the battery type Set this when you replace the battery or connect an external battery Proceed to 3 16 Resetting Battery Information page ...

Page 20: ... are heard LEDs that blink when the 90 days setting is selected Setting Setting LED Description 180 days Check batteries every 180 days 90 days Check batteries every 90 days 30 days Check batteries every 30 days None No battery check Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly un...

Page 21: ...remaining life accumulated battery operating time number of power outages battery exhaustion LED indicator when you replace the battery Default setting The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redisplayed Tip The battery information should be reset when the b...

Page 22: ...thout delay in response to ON OFF operations on the remote switch Delay Enable linked operation ON OFF delay times ON OFF occur after the specified time in response to ON OFF operations on remote switch When No delay is selected the delay times set in 3 18 Setting Linked Operation ON Delay Times and 3 19 Setting Linked Operation OFF Delay Times are disabled Press The blinking pattern changes each ...

Page 23: ...e specified time following an ON operation on the remote switch The specified ON delay time is enabled only when Delay is specified in 3 17 Enabling and Disabling Linked Operation Delay Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LED blinking pattern is redisplayed Tip Press Defa...

Page 24: ...e switch OFF operation differs depending on the value set in 3 5 Setting PC Interface For details see 18 2 4 Linked Operation System Configuration in the E11A Instruction Manual The specified OFF delay time is enabled only when Delay is specified in 3 17 Enabling and Disabling Linked Operation Delay Default setting Press The blinking pattern changes each time you press or If you miss the LED blink...

Page 25: ...you want to perform output line control The settings of 3 21 to 3 27 are disabled when you select Disabled If after specifying and confirming Enabled you then change the setting to Disabled and restart the UPS the output delay times set with 3 21 to 3 24 return to the default values Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you w...

Page 26: ... when you specify Enabled in 3 20 Enabling and Disabling Output line Control If after specifying and confirming Enabled you then change the setting to Disabled and restart the UPS the ON delay time set with this menu item returns to the default value of 0 seconds Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select contin...

Page 27: ...e is enabled only when you specify Enabled in 3 20 Enabling and Disabling Output line Control If after specifying and confirming Enabled you then change the setting to Disabled and restart the UPS the ON delay time set with this menu item returns to the default value of 0 seconds Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want...

Page 28: ...ly when you specify Enabled in 3 20 Enabling and Disabling Output line Control If after specifying and confirming Enabled you then change the setting to Disabled and restart the UPS the OFF delay time set with this menu item returns to the default value of 0 seconds Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select con...

Page 29: ...ly when you specify Enabled in 3 20 Enabling and Disabling Output line Control If after specifying and confirming Enabled you then change the setting to Disabled and restart the UPS the OFF delay time set with this menu item returns to the default value of 0 seconds Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select con...

Page 30: ...time is enabled only when you specify Standalone in 3 5 Setting PC Interface and Enabled in 3 20 Enabling and Disabling Output Line Control Power supply continues if utility power is restored during the specified time Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LE...

Page 31: ...time is enabled only when you specify Standalone in 3 5 Setting PC Interface and Enabled in 3 20 Enabling and Disabling Output Line Control Power supply continues if utility power is restored during the specified time Default setting Press The blinking pattern changes each time you press or If you miss the LED blinking pattern you want to select continue pressing the button repeatedly until the LE...

Page 32: ...ng Stopped by 3 26 Setting the Outlet Box OUTPUT2 Power Outage Output Time setting However when an OFF operation is performed with on the front panel or with the remote switch Interface setting Standalone then output from OUTPUT0 stops following the stopping of OUTPUT1 and OUTPUT2 even if Continue power supply is selected This setting is enabled only when Enabled is selected in 3 20 Enabling and D...

Page 33: ...Ring signal when the UPS starts Do not output Do not output a Ring signal Some computers do not start automatically by power supply only Setting this item to Output allows you to automatically start such a computer when the UPS starts This function is enabled only for computers that support a Wake Up on Ring function Default setting Press The blinking pattern changes each time you press or If you ...

Page 34: ...UPS restarts If you change any of these items stop the UPS and start it again See 11 3 UPS Shutdown If Not to Be Used for More Than a Week in the E11A Instruction Manual for the shutdown procedure and see 11 1 UPS Startup in the E11A Instruction Manual for the startup procedure Always shut down connected loads before shutting the UPS down Note that the changes to items in 3 13 Setting Battery Back...

Page 35: ...rred to as 001 model and 021 model etc or E11A and E11A T as shown in the table below depending on the item explained Model UL standard Model Model name in the Use Settings Guide E11A 001 E11A U001J E11A U001 001 model E11A 002 E11A U002J E11A U002 002 model E11A 011 E11A U011J E11A U011 011 model E11A 012 E11A U012J E11A U012 012 model E11A 021 E11A U021J E11A U021 021 model E11A E11A 001TW E11A ...

Reviews: