VOC SENSOR 

Remove the cover. 

Connect the 3 wires from the sensor to the same color wiring 
coming from the unit. Use the wire connectors (marrettes) 
included.  

PROCESS:

 When the unit turns on, the GREEN LED flashes for 5 

minutes preheat time. Then the RED LED blinks repeatedly, 
indicating that the sensor is sampling the air. If the RED LED 
remains lit, the relay opens then triggers on the oxidizing lamp 
(all UVV). 

If the RED LED goes out, the oxidizing lamp is not lit. 

SETTING (if necessary) 

You will need a voltmeter with alligator probes. 

Place the probes one on the positive terminal, the other on the neutral terminal. 

Use a small screwdriver to turn the adjustment screw to increase the sensitivity of the sensor. 
The default setting is 3.4 vdc. The closer your setting is to 3.4 vdc, the faster the trigger will be. 

 

 

 

MAINTENANCE INSTRUCTIONS 

 

Change pre 

filter (part # MSCFTR2) regularly each month (or few weeks depending on number 

of smokers) since it will fill rapidly with nicotine dust and will prevent a good airflow. Check the 
filters after the first 2 -3 weeks of installation. The 4 inches filter can be discarded when full: the 
pre-filters will be enough to prevent the coating of the fan. 

 

Every 3 months, check the lamps: if they are covered with dust, clean them with denatured 
alcohol. 

 

Change lamps to maintain performance: make sure to put the same lamp in the same clamp. Do 
not interchange lamps as the blue end cap lamp works only with the VOC sensor. 

o

 

LMPHGXJ160- Dual zone lamp (yellow end cap) change every 2 years 

o

 

LMPHXJ160- All oxidation lamp (blue end cap) change every year 

 

Recalibrate or change the VOC monitor board every 3-4 years 
 

 

 

setting screw: 

triggers at  

 3.4 V DC 

Positive 

 

Neutral  

 

Summary of Contents for S1000FX-GX

Page 1: ...ted in BX shield One 1 VOC sensor Fig 2 factory pre set LAMP INSTALLATION this step can be done later 1 Open the front door on the unit 2 Open the door access to the aluminum box by removing the two wing nuts see picture aside 3 Remove the BLUE END CAP LMPHXJ160 lamp from packaging use the gloves provided 4 Identify the ballast showing LMPHXJ160 follow the wire and insert it in the appropriate cla...

Page 2: ...ell you it works IMPORTANT you may have to calibrate the VOC Monitor refer to the monitor instructions or call Sanuvox WORKING INSTRUCTION The VOC sensor analyzes the air every 90 seconds A 20 foot power cord connects it via a relay to the device to activate the second oxidizing lamp on demand The S300 unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC U...

Page 3: ... closer your setting is to 3 4 vdc the faster the trigger will be MAINTENANCE INSTRUCTIONS Change pre filter part MSCFTR2 regularly each month or few weeks depending on number of smokers since it will fill rapidly with nicotine dust and will prevent a good airflow Check the filters after the first 2 3 weeks of installation The 4 inches filter can be discarded when full the pre filters will be enou...

Page 4: ...he VOC sensor analyzes the air every 90 seconds A 20 foot power cord connects it via a relay to the device to activate the second oxidizing lamp on demand The S1000 unit runs continuously so its regular lamp purifies the air constantly This dual zone lamp UVC UVV is enough when there are only one or two smokers However when cigarette smokes increase in the room the VOC monitor that samples the air...

Reviews: