VOC SENSOR
Remove the cover.
Connect the 3 wires from the sensor to the same color wiring
coming from the unit. Use the wire connectors (marrettes)
included.
PROCESS:
When the unit turns on, the GREEN LED flashes for 5
minutes preheat time. Then the RED LED blinks repeatedly,
indicating that the sensor is sampling the air. If the RED LED
remains lit, the relay opens then triggers on the oxidizing lamp
(all UVV).
If the RED LED goes out, the oxidizing lamp is not lit.
SETTING (if necessary)
You will need a voltmeter with alligator probes.
Place the probes one on the positive terminal, the other on the neutral terminal.
Use a small screwdriver to turn the adjustment screw to increase the sensitivity of the sensor.
The default setting is 3.4 vdc. The closer your setting is to 3.4 vdc, the faster the trigger will be.
MAINTENANCE INSTRUCTIONS
•
Change pre
–
filter (part # MSCFTR2) regularly each month (or few weeks depending on number
of smokers) since it will fill rapidly with nicotine dust and will prevent a good airflow. Check the
filters after the first 2 -3 weeks of installation. The 4 inches filter can be discarded when full: the
pre-filters will be enough to prevent the coating of the fan.
•
Every 3 months, check the lamps: if they are covered with dust, clean them with denatured
alcohol.
•
Change lamps to maintain performance: make sure to put the same lamp in the same clamp. Do
not interchange lamps as the blue end cap lamp works only with the VOC sensor.
o
LMPHGXJ160- Dual zone lamp (yellow end cap) change every 2 years
o
LMPHXJ160- All oxidation lamp (blue end cap) change every year
•
Recalibrate or change the VOC monitor board every 3-4 years
setting screw:
triggers at
3.4 V DC
Positive
Neutral