5
Instruction Manual for R Max
1-888-726-8869
www.sanuvox.com
3. While holding the porcelain end-cap (with 4 pins), carefully push the
white connector onto the four pins. The connector will fit into position.
NOTE:
Too much force applied from the opposite end-cap may break
the lamp.
4. Slide the UV lamp porcelain end-cap (with 4 pins) in the aluminum
tube of the unit, then through the clamp.
STEP 3
STEP 4
STEP 5
STEP 6
5. Once the UV lamp is inserted, release the clamp to fix the lamp in place.
6. Once the UV lamp is installed, place the turbulator on top of the reflecting
chamber securing it with 2 screws provided in the installation kit. It is
important to note that the air should first flow through the turbulator
before moving in front of the UV lamp.
STEP 7
7. Prepare the duct (return or supply) for installation. Evaluate the ideal area
for installing the air purifier. The reflection chamber should always be
parallel to the airflow. Ensure that the purifier will fit into the plenum and
position it keeping in mind to minimize plastic exposure to direct UV light.
CAUTION:
Before installing or performing maintenance on the unit
or system,
TURN OFF AND DISCONNECT the unit or system from
all power sources
(there may be more than one switch to disconnect).