8
Instruction Manual for BIO-WALL™
1-888-726-8869
www.sanuvox.com
STEP 17
STEP 18
STEP 19
17. Pull on each wire to ensure a firm connection, then repeat steps 15-16-
17 for the next 4 segments.
Connect Limit Switch to 5 VDC Circuit
18. Referring to the electrical diagram, identify the SW and 5 VDC terminals
on the electronic board terminal block.
Insert two control wires into it and connect them to the limit switch. In this
way, if the switch is activated, the electronic circuit will cut off the power
supply.
NOTE:
Remember to put the YELLOW WARNING stickers on the access door.
Interconnection to Building Management System (BMS) or
BioSmart Touch Screen (optional)
NOTE:
The addition of control wires or a touch screen is not necessary
for the operation of the BIO-WALL™.
19.If you have purchased a BioSmart touch screen, now is the time to
connect it to your ballast box. Follow the instructions provided with the
screen.
NOTE:
Each BioSmart display has been configured for a specific BIO-
WALL™. Be sure to identify the correct one.
Furthermore, if you wish to share the information with a management
controller, SANUVOX offers 3 BMS operating modes: an external 24
VDC power supply will be required. Please refer to the “OPERATION”
section.
STEP 20
Certified Electrician Required to Power Ballast Box
20. The power supply can be 120V or 240V (optional), to a circuit breaker
with a minimum of 10A. You only have to connect the black and white
wires as well as the ground.
NOTE: In certain circumstances, a manual circuit breaker can also be
installed near the ballast box.
Once the power is supplied, replace the cover and secure it in place by
turning the 4 screws to the right.
You are now ready to enjoy
superior indoor air quality and safety.