12
Instruction Manual for BIO-WALL™
1-888-726-8869
www.sanuvox.com
FIG. 2
FIG. 3
FIG. 1
Step by Step Change of Operation Mode
By default
1. Turn off the power at the ballast box.
2. Remove the cover by turning the 4 screws to the left.
3. Locate the section in
Figure 1.
4. Turn power back on:
all LEDs will flash for 5 seconds.
Then, a specific sequence will be displayed in RED and GREEN for 5
seconds to indicate the selected operation mode:
Mode 1
G
R
R
R
R
Mode 2
R
G
R
R
R
Mode 3
R
R
G
R
R
The second LED will be GREEN (see
Figure 2
) to indicate that the BIO-
WALL™ is in Mode 2, which is the default mode.
5. After this last 5 seconds, all LEDs will turn GREEN (see
Figure 3) to
indicate that the mode is saved.
To change the mode
1. Repeat steps 1-4 above.
2. While the mode sequence is displayed (you have 5 seconds), press the
button: each time, you will change modes.
3. When you have selected the desired mode, wait 5 seconds for it to be
saved.
Remote control (BMS) or limit switch on access door
A wire jumper is factory-installed on the PLC and PLC24 terminals: this configuration automatically turns on the lamps when
the box is powered.
If you want to turn on the lamps remotely, remove the wire jumper and connect a pair of wires to these contacts: sending a 5V
- 24 VDC signal will turn on the lamps and its interruption (0V) will turn them off.
You can also, for added security, connect these wires to a limit switch on the access door, which will only require a 5V supply.
CAUTION: In Mode 3
, if you wish to light the lamps with the BMS, you must move the jumper to the right (see
Figure 1 of
‘Step by Step Change of Operation Mode’) and connect your wires to the PLC contact and 0V.
Button
Wire-jumper
Summary of Contents for Bio-Wall MAX