Santon PremierPlus 100 Installation And Servicing Instructions Download Page 8

8

(D2) to be connected.

3.60    The discharge pipe should not be connected 

to a soil discharge stack unless it can be demonstrated 

that that the soil discharge stack is capable of safely 

withstanding temperatures of the water discharged, 

in which case, it should:

 (a)    contain a mechanical seal, not incorporating 

a  water  trap,  which  allows  water  into  the  branch 

pipe without allowing foul air from the drain to be 

ventilated through the tundish;

 (b)     be a separate branch pipe with no sanitary 

appliances connected to it;

 (c)      if plastic pipes are used as branch pipes carrying 

discharge from a safety device they should be either 

polybutalene (PB) to Class S of BS 7291-2:2006 or 

cross  linked  polyethylene  (PE-X)  to  Class  S  of  BS 

7291-3:2006; and

(d)    be  continuously  marked  with  a  warning  that 

no sanitary appliances should be connected to the 

pipe.

Note: 

1.  Plastic pipes should be joined and assembled with 

fittings  appropriate  to  the  circumstances  in  which 

they are used as set out in  BS EN ISO 1043-1.

2.   Where pipes cannot be connected to the stack it 

may be possible to route a dedicated pipe alongside 

or in close proximity to the discharge stack.

Termination of discharge pipe

3.61      The  discharge  pipe  (D2)  from  the  tundish 

should terminate in a safe place where there is no risk 

to persons in the vicinity of the discharge.

3.62    Examples of acceptable discharge arrangements 

are:

(b)   to a trapped gully with the end of the pipe below 

a fixed grating and above the water seal;

(c)   downward discharges at low level;  i.e. up to 

100mm  above  external  surfaces  such  as  car  parks, 

hard  standings,  grassed  areas  etc.  are  acceptable 

providing  that  a  wire  cage  or  similar  guard  is 

positioned  to  prevent  contact,  whilst  maintaining 

visibility;  and

(d)      discharges  at  high  level:    e.g.  into  a  metal 

hopper  and  metal  downpipe  with  the  end  of  the 

discharge pipe clearly visible or onto a roof capable 

of withstanding high temperature discharges of water 

and 3m from any plastic guttering system that would 

collect such discharges. 

3.63  The discharge would consist of high temperature 

water  and  steam.    Asphalt,  roofing  felt  and  non-

metallic rainwater goods may be damaged by such 

discharges.

Worked example of discharge pipe sizing

Fig. 5, page 9: shows a G1/2 temperature relief valve 

with  a  discharge  pipe  (D2)  having  4  No.  elbows 

and length of 7m from the tundish to the point of 

discharge.

From Table 3, page 9:

Maximum resistance allowed for a straight length of 

22mm copper discharge pipe (D2) from a G1/2

temperature relief valve is 9.0m.

Subtract  the  resistance  for  4  No.  22mm  elbows  at 

0.8m each = 3.2m

Therefore the permitted length equates to: 5.8m

5.8m is less than the actual length of 7m therefore 

calculate the next largest size.

Maximum  resistance  allowed  for  a  straight  length 

of 28mm pipe (D2) from a G1/2 temperature relief 

valves equates to 18m.

Subtract  the  resistance  of  4  No.  28mm  elbows  at 

1.0m each = 4.0m

Therefore  the  maximum  permitted  length  equates 

to: 14m 

As the actual length is 7m, a 28mm (D2) copper pipe 

will be satisfactory.

WARNINGS:

Under  no  circumstances  should  the  factory 

• 

fitted  temperature/pressure  relief  valve  be 

removed other than by a competent  person. To 

do so will invalidate any guarantee or claim.

The  cold  water  combination  valve  assembly 

• 

must be fitted on the PremierPlus water supply 

to the PremierPlus cylinder.

No control or safety valves should be tampered 

• 

with or used for any other purpose.

The discharge pipe should not be blocked or 

• 

used for any other purpose.

The tundish should not be located adjacent to 

• 

any electrical components.

Summary of Contents for PremierPlus 100

Page 1: ...r s and thermal controls l Factory fitted temperature pressure relief valve l Cold water combination valve assembly l Expansion vessel and mounting bracket l Tundish l Motorised valve indirect models...

Page 2: ...istance The outer casing is a combination of resilient thermoplastic mouldings and plastic coated corrosion proofed steel sheet All products are insulated with CFC free polyurethane foam to give good...

Page 3: ...55 Indirect 100 125 25 120 147 27 150 184 31 170 203 33 210 251 41 250 300 50 300 360 60 Table1 unit weights WATER SUPPLY Bear in mind that the water supply to the property will be supplying both the...

Page 4: ...unit The fittings are threaded 3 4 BSP male parallel should threaded pipe connections be required COLD FEED A 22mm cold water supply is recommended however if a 15mm 1 2 supply exists which provides...

Page 5: ...old feed to the unit A swept tee joint is available as an accessory order code no 94 970 033 The secondary return pipe should be in 15mm pipe and incorporate a check valve to prevent backflow A suitab...

Page 6: ...00 1090 16 4 27 21 170 306 925 1216 173 170 315 354 925 1216 16 0 30 24 210 306 1184 1474 215 210 315 354 1184 1474 18 3 34 26 250 306 1394 1726 257 250 315 354 1391 1726 20 38 27 300 306 1715 2040 31...

Page 7: ...that is used by the safety devices the manifold should be factory fitted as part of the hot water storage system unit or package Tundish 3 54 The tundish should be vertical located in the same space a...

Page 8: ...prevent contact whilst maintaining visibility and d discharges at high level e g into a metal hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of wi...

Page 9: ...outlet sizes NOTE The above table is based on copper tube Plastic pipes may be of different bore and resistance Sizes and maximum lengths of plastic should be calculated using data prepared for the t...

Page 10: ...suitable controller to BSEN 60730 The PremierPlus MUST be earthed All wiring to the unit must be installed in accordance with the latest IEE Wiring Regulations and the circuit must be protected by a s...

Page 11: ...with a contact separation of at least 3mm in both poles All connections are made to the terminal block located under the terminal cover mounted on the side of the unit The supply cable s must be rout...

Page 12: ...1 N 2 3 HTG ON DHW ON L N 2 3 1 L 2 N 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Supply 1 2 3 G W Bl 2 0 GY 3 G 1 Br Bl 2 0 L N Programmer Boiler Pump Zone valve HTG Premier Plus terminal block 1 3 2 2 Ro...

Page 13: ...he temperature can be adjusted by inserting a flat bladed screwdriver in the adjustment knob on top of the immersion heater thermostat and rotating The adjustment range 1 to 5 represents a temperature...

Page 14: ...r time the immersion heater gasket may become stuck to the mating surface To break the seal insert a round bladed screwdriver into one of the pockets on the immersion heater and gently lever up and do...

Page 15: ...LY BEFORE OPENING THE COVER S Temperature adjustment is made by inserting a flat bladed screwdriver in the slot on the adjustment disc on top of the thermostat and rotating The adjustment range 1 to 5...

Page 16: ...pply off 2 Check and open stock cock 2 Strainer blocked 2 Turn off water supply Remove strainer and clean see maintanance section 3 Cold Water Combination Valve incorrectly fitted 3 Check and refit as...

Page 17: ...ion body 95 605 900 10 Pressure reducing valve cartridge 3 5bar 95 605 898 11 Temperature Pressure Relief Valve 95 605 810 12 Expansion vessel 12 litre 100 120 and 150 litre models 95 607 863 13 Expan...

Page 18: ...losses based on an ambient air temperature of 20 C and a stored water temperature of 65 C ENVIROMENTAL Products are manufactured from many recyclable materials At the end of their useful life they sho...

Page 19: ...d to frost nor has it been tampered with or been subjected to misuse or neglect No factory fitted parts have been removed for unauthorised repair or replacement The BenchmarkTM Commissioning Checklist...

Page 20: ...20 notes...

Page 21: ...21 notes...

Page 22: ...22...

Page 23: ...23...

Page 24: ...Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 0208 5730574 Parts Center Network 65 Business Park Bentley Wood Way Burnley Lancashire BB11 5ST Tel 01282 834403 www partscenter co uk Ne...

Reviews: