LIMITATIONS

The  PremierPlus  cylinder  should  not  be  used  in 

association with any of the following:

Solid fuel boilers or any other boiler in which the 

• 

energy input is not under effective thermostatic 

control,  unless  additional  and  appropriate 

safety measures are installed.

Ascending spray type bidets or any other class 

• 

1 back syphonage risk require that a type  A air 

gap be employed.

Steam  heating  plants  unless  additional  and 

• 

appropriate safety devices are installed.

Situations  where  maintenance  is  likely  to  be 

• 

neglected or safety devices tampered with.

Water  supplies  that  have  either  inadequate 

• 

pressure  or  where  the  supply  may  be 

intermittent.

Situations where it is not possible to safely pipe 

• 

away any discharge from the safety valves.

In areas where the water consistently contains 

• 

a  high  proportion  of  solids,  e.g.  suspended 

matter  that  could  block  the  strainer  unless 

adequate filtration can be ensured. 

OPERATIONAL SUMMARY

Maximum PremierPlus pressure 

16 bar

Operating pressure 

3.5 bar

Expansion vessel pressure 

3.5 bar

Expansion relief valve setting 

6 bar

T&P relief valve setting 

90°C/10 bar

Maximum primary circuit (pressure  3 bar (indirect 

only)

Storage capacity 

See Table1

Weight when full 

See Table1

INSTALLATION – GENERAL 

PIPE FITTINGS 

All  pipe  fittings  are  made  via  22mm  compression 

fittings directly to the unit. The fittings are  threaded 

3/4”BSP  male  parallel  should  threaded  pipe 

connections be required.  

COLD FEED

A  22mm  cold  water  supply  is  recommended, 

however,  if  a  15mm  (1/2”)  supply  exists,  which 

provides sufficient flow, this may be used (although 

more flow noise may be experienced). 

A stopcock or servicing valve should be incorporated 

into the cold water supply to enable the PremierPlus 

cylinder  and  its  associated  controls  to  be  isolated 

and serviced.

COLD WATER COMBINATION VALVE ASSEMBLY (FIG. 

2, page 4)

The Cold Water Combination Valve can be connected 

anywhere on the cold water PremierPlus supply prior 

to the Expansion Vessel (see Fig. 6, page 10). The Cold 

Water Combination Valve is installed as a complete 

one-piece unit. The valve  incorporates the Pressure 

Reducer, Strainer,  Expansion  Valve and Check Valve. 

Ensure that the valve is installed with the direction of 

flow arrows pointing in the right direction. No other 

valves  should  be  placed  between  the  Cold  Water 

Combination  Valve  and  the  PremierPlus  unit.  The 

Expansion  Valve  connection  must  not  be  used  for 

any other purpose. 

Expansion valve

Cold mains 

connection

(22mm)

Expansion valve

outlet (15mm)

Outlet connection

(22mm)

Pressure reducing

valve cartridge

(3.5bar)

Fig. 2: Cold water combination valve

DRAIN TAP

A suitable draining tap should be installed in the cold 

water  supply  to  the  PremierPlus  cylinder  between 

the expansion valve (see Fig. 6) and the heater at as 

low a level as possible. It is recommended that the 

outlet point of the drain pipework be at least 1 metre 

Summary of Contents for PremierPlus 100

Page 1: ...r s and thermal controls l Factory fitted temperature pressure relief valve l Cold water combination valve assembly l Expansion vessel and mounting bracket l Tundish l Motorised valve indirect models...

Page 2: ...istance The outer casing is a combination of resilient thermoplastic mouldings and plastic coated corrosion proofed steel sheet All products are insulated with CFC free polyurethane foam to give good...

Page 3: ...55 Indirect 100 125 25 120 147 27 150 184 31 170 203 33 210 251 41 250 300 50 300 360 60 Table1 unit weights WATER SUPPLY Bear in mind that the water supply to the property will be supplying both the...

Page 4: ...unit The fittings are threaded 3 4 BSP male parallel should threaded pipe connections be required COLD FEED A 22mm cold water supply is recommended however if a 15mm 1 2 supply exists which provides...

Page 5: ...old feed to the unit A swept tee joint is available as an accessory order code no 94 970 033 The secondary return pipe should be in 15mm pipe and incorporate a check valve to prevent backflow A suitab...

Page 6: ...00 1090 16 4 27 21 170 306 925 1216 173 170 315 354 925 1216 16 0 30 24 210 306 1184 1474 215 210 315 354 1184 1474 18 3 34 26 250 306 1394 1726 257 250 315 354 1391 1726 20 38 27 300 306 1715 2040 31...

Page 7: ...that is used by the safety devices the manifold should be factory fitted as part of the hot water storage system unit or package Tundish 3 54 The tundish should be vertical located in the same space a...

Page 8: ...prevent contact whilst maintaining visibility and d discharges at high level e g into a metal hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of wi...

Page 9: ...outlet sizes NOTE The above table is based on copper tube Plastic pipes may be of different bore and resistance Sizes and maximum lengths of plastic should be calculated using data prepared for the t...

Page 10: ...suitable controller to BSEN 60730 The PremierPlus MUST be earthed All wiring to the unit must be installed in accordance with the latest IEE Wiring Regulations and the circuit must be protected by a s...

Page 11: ...with a contact separation of at least 3mm in both poles All connections are made to the terminal block located under the terminal cover mounted on the side of the unit The supply cable s must be rout...

Page 12: ...1 N 2 3 HTG ON DHW ON L N 2 3 1 L 2 N 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Supply 1 2 3 G W Bl 2 0 GY 3 G 1 Br Bl 2 0 L N Programmer Boiler Pump Zone valve HTG Premier Plus terminal block 1 3 2 2 Ro...

Page 13: ...he temperature can be adjusted by inserting a flat bladed screwdriver in the adjustment knob on top of the immersion heater thermostat and rotating The adjustment range 1 to 5 represents a temperature...

Page 14: ...r time the immersion heater gasket may become stuck to the mating surface To break the seal insert a round bladed screwdriver into one of the pockets on the immersion heater and gently lever up and do...

Page 15: ...LY BEFORE OPENING THE COVER S Temperature adjustment is made by inserting a flat bladed screwdriver in the slot on the adjustment disc on top of the thermostat and rotating The adjustment range 1 to 5...

Page 16: ...pply off 2 Check and open stock cock 2 Strainer blocked 2 Turn off water supply Remove strainer and clean see maintanance section 3 Cold Water Combination Valve incorrectly fitted 3 Check and refit as...

Page 17: ...ion body 95 605 900 10 Pressure reducing valve cartridge 3 5bar 95 605 898 11 Temperature Pressure Relief Valve 95 605 810 12 Expansion vessel 12 litre 100 120 and 150 litre models 95 607 863 13 Expan...

Page 18: ...losses based on an ambient air temperature of 20 C and a stored water temperature of 65 C ENVIROMENTAL Products are manufactured from many recyclable materials At the end of their useful life they sho...

Page 19: ...d to frost nor has it been tampered with or been subjected to misuse or neglect No factory fitted parts have been removed for unauthorised repair or replacement The BenchmarkTM Commissioning Checklist...

Page 20: ...20 notes...

Page 21: ...21 notes...

Page 22: ...22...

Page 23: ...23...

Page 24: ...Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 0208 5730574 Parts Center Network 65 Business Park Bentley Wood Way Burnley Lancashire BB11 5ST Tel 01282 834403 www partscenter co uk Ne...

Reviews: