5. INSTALLATION
11
1) Wiring for single-phase input
Note
※
:
For the single-phase input wiring, the live (L) wire must be connected to the R-phase of
the input terminals, not to the S or T phase terminal, otherwise, the UPS will consider
the utility power abnormal
2) Wiring for three-phase input
Note
※
:
Make sure that the phase sequence is correct for three-phase mains input wiring, If the
phase sequence is wrong, the UPS cannot start up and will emit warning alarm and the
LCD will display
“
phase sequence error”. The N wire of mains input must be connected
to the N terminal of the input for input wiring of the UPS system!
Remark: the three phases
are marked with R, S and T.
If adopting A, B and C mark,
the R-phase, S-phase and
T-phase correspond to the
A-phase, B-phase and
C-phase.
L N G
UPS
R S T N L N
+
G
G
L N G
Mains input
Distribution Panel
Mains input
Breaker
battery
Input
Out put
To load
Output
Breaker
Output
Distribution Panel
Single-phase Input Connection Diagram
N G
UPS
R S T N L N
+
G
G
L N G
R S T
b attery
Input
Output
Three-phase input connection diagram
Mains input
Distribution Panel
Mains input
Breaker
Output
Breaker
Output
Distribution Panel
To load