SANJIANG SEC3002 Installation & Commissioning Manual Download Page 4

SEC3002 FIRE ALARM CONTROL PANEL

Page 3 of 24

F.P.E. Out (+, -)
F.A. Out (+, -)

Output voltage

18.5

~

27.5VDC

Max. output current

0.5A

Fuse rating

F1AL250V

End of line resistor

4K7

Type of cable

Plain unscreened cable, 1.5mm

2

Cable diameter

1mm

2

~

2mm

2

Transmission distance

1500m

Fault Out
(NC, COM, NO)

Contact capacity

30VDC@2A, [email protected]

Type of cable

Plain unscreened cable, 1.5mm

2

Cable diameter

1mm

2

~

2mm

2

24VK (+, -)

Output voltage

18.5 ~ 27.5VDC

Max. output current

0.6A

Fuse rating

F1AL250V

Type of cable

Plain unscreened cable, 1.5mm

2

Cable diameter

1mm

2

~

2mm

2

Input

Class change (+, -)

Input mode

Passive

Cable resistance

500

Ω

Type of cable

Plain unscreened cable, 1.5mm

2

Cable diameter

1mm

2

~

2mm

2

Loop

Loop Out (+, -)
Loop In (+, -)

Output voltage

16.5

~

27.5VDC, pulse

Output current

0

~ 0.3

A

Loop type

Class A

Type of cable

Screened or unscreened twisted-pair, 1.5mm

2

Transmission distance

1000m

Cable diameter

1mm

2

~

2mm

2

Network communication

RS-485

Max. number of FIPs

30

Transmission rate

9600 bps

Type of cable

Screened or unscreened twisted-pair, 1mm

2

Transmission distance

1000m

Cable diameter

1mm

2

~

5mm

2

CAN

Max. number of panels

20

Transmission rate

Optional: 10K, 20K, 50K and 100K bps

Type of cable

Screened or unscreened twisted-pair, 1mm

2

Transmission distance

1000m

Cable diameter

1mm

2

~

5mm

2

Physical dimensions

Approx. Dimensions of the panel (W

×

H

×

D)

430×560×170mm

Approx. weight (without battery)

12kg

Operating conditions

Temperature range: 0

°

C

~

45

°

C; Max relative humidity: 95% (40

°

C

±

2

°

C, no condensation)

Summary of Contents for SEC3002

Page 1: ......

Page 2: ...l connections 7 4 Indications and Controls 8 4 1 LED indicators 8 4 2 Button controls 9 4 3 Zone indication and control panel 10 5 Commissioning and Programming 10 5 1 Overview 10 5 2 Functions availa...

Page 3: ...essable fire detection panel with 1 loop of 324 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specification...

Page 4: ...cable 1 5mm2 Cable diameter 1mm2 2mm2 Loop Loop Out Loop In Output voltage 16 5 27 5VDC pulse Output current 0 0 3A Loop type Class A Type of cable Screened or unscreened twisted pair 1 5mm2 Transmis...

Page 5: ...rd In general the SEC3002 consists of 2 sections 1 The right internal section contains the main processor of A Board the I O communication interface of B Board the Buttons and LEDs Board the ZCP board...

Page 6: ...Communication Board optional This board is optional for external communication with other panels or FIPs fire indicating panel Specifically up to 20 panels can be networked with each other through th...

Page 7: ...NOT connect batteries before applying mains power first 3 5 Points connection to the loop The figure in next page shows a typical loop connection complete with detectors sounder strobes modules and l...

Page 8: ...the wiring to be monitored If the circuit is unused the 4K7 resistor must still be connected A typical connection is shown below 2 Fault Out short for Fault Output The NO and COM are closed in normal...

Page 9: ...refers to a 24V power supply It provides 24V output continuously and disconnects the power for about 2 seconds at the time the panel is reset 6 Class Change A programmable input By shorting this term...

Page 10: ...disabled and flashes when it has a fault Disable has priority over fault F P E DISABLED Lit yellow to indicate the F P E Out is disabled 4 2 Button controls 0 9 Used to enter numbers letters and marks...

Page 11: ...re is any fault with the zone it lights steadily when the zone is in disablement or test condition The control button then is used to activate sounders in that zone Note Each unit of LEDs with a butto...

Page 12: ...panel will receive and display alarm signals from that panel In network the time of the system is based on the time of the central panel that is when the time of Host 1 is changed time on other netwo...

Page 13: ...igned to Up to 30 FIPs can be included in this system The setting window is as below Printer setup The standard printer of PRINTER 02 compatible to the panel can be registered through the menu option...

Page 14: ...e to the loop with a unique Address number The following is the setup for the Product Type of a detector Since the Product Type is an inherent attribute of a field device the optional product types pr...

Page 15: ...e consider the detection zone as the same area of the alarm zone with the same zone number The Output Mode refers to the control mode of an output type module when transmitting signal to its following...

Page 16: ...setup the Causes apply to all devices in the system Press Add to create a rule and press Del to delete one To enable a c e press the Reg The default value of Num of fire signal is 01 which means once...

Page 17: ...ers Additionally for convenience of customized function the button s utility can be defined additionally The setup window is shown below It is always recommended that the default settings be registere...

Page 18: ...ble point in real time When selected you will be prompted to enter the specific address of the device you want to put into test Enter the target point and press OK to start the point test Module start...

Page 19: ...o the detector module setup window with the Reg and Product Type data overwritten by the new auto learned data which means the previous system configuration will be changed So take care about this bef...

Page 20: ...follow its tips Update system The system allows to be updated on site with additional functions by using a U disk at the authorized engineer level for future development Copy the file needed to the U...

Page 21: ...IP In which The multiplier 1 25 is present to account for loss of capacity over the life of the battery IFq 0 3A which is the quiescent current of the fire alarm control panel in the event of the los...

Page 22: ...er to the panel but the LCD display is off and panel does not work Possible reason and solution check if the fuse on the PSE Filter blows out Check if the POWER indicator on the front panel is on othe...

Page 23: ...use is slipped over the pins accordingly Problem no indication is given by the ZCP when there is a zonal fire zonal fault etc Possible reason and solution the setup for ZCP is not registered The ZCP c...

Page 24: ...Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventional Ionizat...

Page 25: ...Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emergency Lightn...

Page 26: ......

Reviews: