8. Connection of bathroom appliances 

To connect a shower/bath, ensure that the trap exit is 
15cm above floor level. Although not obligatory, a lid 
connection may be used to run an external air vent.

9. Discharge connection

Note:

 The discharge pipework should be 32mm copper 

or rigid solvent weld plastic.
Observe the pumping parameters of the unit (vertical 
and horizontal combination, step 4).

All horizontal pipe runs must have a minimum fall of 
1:100 (10mm per metre) all the way to the drain.

Technical advice for discharge to lower floor

If the discharge pipework runs to a level considerably 
lower than the unit, the resultant siphoning effect 
can suck out the water seal in the unit. Fitting an air 
admittance valve capable of withstanding 10psi pressure 
(BBA approved) at the high point of the pipe run will 
overcome this problem.

Orient the opening end of the non-return valve in the 
direction of the discharge. Secure with the metal hose 
clip (

F

). 

10. In case of servicing

For possible service requirements, provide a drain off at 
the low point of the installation.

15 cm

3

7

3

3%

3%

3%

3%

Summary of Contents for SANISPEED

Page 1: ... follow instructions could result in poor functioning of the unit This equipment benefits from the latest technological innovations concerning soundproofing To benefit fully from the advantages provided by this new generation of appliances it is important to comply with the installation instructions in section 5 2 List of Accessories included A B C E F G I x2 Discharge elbow D Air vent cover Metal...

Page 2: ...6 mm 185 mm 92 5 mm 139 4 mm Vertical Height metres Flow Rate L min max 70m 2m 3m 4m 5m This unit is for domestic use only 4 Performance Curve Height and Length of the discharge pipe 6m Max 7m max 20m max 10m 1 2 3 4 5 6 7 8 3 7 20 30 40 50 60 70 80 90 100 110 120 ø 32 The discharge pipe size for Sanispeed must be 32mm ...

Page 3: ... of the piperun I H 6 Connection to side inlets Use the rubber connector A for connection of pipes to the side inlets Secure with the metal hose clips G Cap off unused inlets with the end caps C provided after greasing the joints I H C G A G C G A G 7 Connection to lid inlets To connect to a lid inlet cut off the sealed cap with a hacksaw and connect using the rubber connector A provided Tighter w...

Page 4: ...of 1 100 10mm per metre all the way to the drain Technical advice for discharge to lower floor If the discharge pipework runs to a level considerably lower than the unit the resultant siphoning effect can suck out the water seal in the unit Fitting an air admittance valve capable of withstanding 10psi pressure BBA approved at the high point of the pipe run will overcome this problem Orient the ope...

Page 5: ...m the power supply before attempting any work on the unit The unit does not require any specific maintenance In case of a service requirement please call the Saniflo service engineer especially for any electrical work 15 Guarantee 2 years guarantee as from its date of purchase subject to correct installation and correct use 11 Electrical connection The electrical installation should be carried out...

Page 6: ...16 Parts ...

Reviews: