background image

Merlin 1500S

                              

 

 

 

 

                             User Guide

 

 

 

Rev: 07    05-19

 

7  

3.5

 

Fire alarm integration  

The Merlin 1500S can be integrated with a fire alarm to close the gas supply automatically in the 
event of a fire.  
 
The volt free fire alarm signal can be wired in series with any remote emergency shut off buttons. 

 

 

4

 

Panel LED status 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
When the system is connected to the mains supply, the Red LED of the S&S Logo located in the 

bottom right corner of the panel will illuminate. When no power is present, this LED will not 
illuminate.  

 

 

Gas On  

When the fans are running at the correct speed and the key switch is turned on, the Merlin 1500S 

will open the gas valve and the green ‘Gas On’ LED will illuminate.

 

 

ON = Gas On  
OFF = Gas Off  
 

 

Supply Fans 

Under normal working the LED will illuminate GREEN. If a supply fan fault is detected, the LED will 

be flashing. After 10 seconds of flashing, the gas supply will shut off. 

ON = OK  
FLASHING = One of the supply fans is not running. 
 

 

Extract Fans  

Under normal working the LED will illuminate GREEN. If an extract fan fault is detected, the LED 

will be flashing. After 10 seconds of flashing, the gas supply will shut off. 

ON = OK  
FLASHING = One of the extract fans is not running 
 
 

Summary of Contents for Merlin 1500S

Page 1: ...Merlin 1500S User Guide Rev 07 05 19 1 Gas Safety Products Merlin 1500S Gas Ventilation Interlock system User Guide Please read this guide carefully and retain for future use...

Page 2: ...FAN EXTRACT FAN PD SWITCHES 4 2 4 BMS OUT 4 2 5 EM REMOTE 4 2 6 GAS DETECTOR 5 2 7 FS 1 2 3 4 5 2 8 CO2 MONITOR 5 2 9 12V DC 5 3 Installation Operation 6 3 1 System ON and OFF 6 3 2 Emergency Shut Off...

Page 3: ...should be removed before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power it will not...

Page 4: ...connections If only one fan is being used the terminals not in use should be left linked out 2 4 BMS OUT Terminal connections are available on the circuit board for connections to Building Management...

Page 5: ...arately which can provide power to the fans when the control panel is switched on 2 8 CO2 MONITOR This terminal can be wired to CO2 monitor to shut off the system in the event of CO2 being at alarm le...

Page 6: ...SEL This is factory set in the OFF position which signals the BMS on gas on gas off When switched to the ON position the 1500S will only signal the BMS on a fault i e fan fault CO2 high level detected...

Page 7: ...not illuminate Gas On When the fans are running at the correct speed and the key switch is turned on the Merlin 1500S will open the gas valve and the green Gas On LED will illuminate ON Gas On OFF Ga...

Page 8: ...Under normal working conditions this LED is off If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal wo...

Page 9: ...l pressure differential switch or current switch VOLT FREE INPUT 9 BMS OUT contacts Normally Closed Common and Normally Open 10 PRESSURE SENSOR Disabled 11 EM REMOTE Remote EM Stop buttons and Fire Al...

Page 10: ...Merlin 1500S User Guide Rev 07 05 19 10...

Page 11: ...Merlin 1500S User Guide Rev 07 05 19 11...

Page 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...

Reviews: