Merlin 1500S

                              

 

 

 

 

                             User Guide

 

 

 

Rev: 07    05-19

 

5  

 
2.6

 

GAS DETECTOR 

These connections can be wired to a Merlin gas detector (LPG, 
natural gas or carbon monoxide) as shown. 
 
If no detector is being used leave the link in between the “

”.  

 
 
 
Refer to your detector guide for more information. 
 
 
 

 

 

2.7

 

FS 1/2/3/4 

This terminal switches when the key is turned on and off.  
 
This can be linked to a fan switch (panel supplied separately) which can 
provide power to the fans when the control panel is switched on.  
 

 

 

 

 

2.8

 

CO2 MONITOR  

This terminal can be wired to CO2 monitor to shut off the system in the 

event of CO2 being at alarm level.  

 
If no CO2 monitor is connected, the panel will ‘beep’ and CO2 LED will 

flash 3 times to indicate this terminal has been disabled.  

 
 

 

 

2.9

 

12V DC  

This is a permanent 12v DC output when there is power at the panel and can 
be used to create a relay switch with the BMS relay output. 
 
This is normally used to power a PM2 current monitor. (Supplied separately)  
Contact your supplier for more information. 

 

 

 

 

 

 

Summary of Contents for Merlin 1500S

Page 1: ...Merlin 1500S User Guide Rev 07 05 19 1 Gas Safety Products Merlin 1500S Gas Ventilation Interlock system User Guide Please read this guide carefully and retain for future use...

Page 2: ...FAN EXTRACT FAN PD SWITCHES 4 2 4 BMS OUT 4 2 5 EM REMOTE 4 2 6 GAS DETECTOR 5 2 7 FS 1 2 3 4 5 2 8 CO2 MONITOR 5 2 9 12V DC 5 3 Installation Operation 6 3 1 System ON and OFF 6 3 2 Emergency Shut Off...

Page 3: ...should be removed before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power it will not...

Page 4: ...connections If only one fan is being used the terminals not in use should be left linked out 2 4 BMS OUT Terminal connections are available on the circuit board for connections to Building Management...

Page 5: ...arately which can provide power to the fans when the control panel is switched on 2 8 CO2 MONITOR This terminal can be wired to CO2 monitor to shut off the system in the event of CO2 being at alarm le...

Page 6: ...SEL This is factory set in the OFF position which signals the BMS on gas on gas off When switched to the ON position the 1500S will only signal the BMS on a fault i e fan fault CO2 high level detected...

Page 7: ...not illuminate Gas On When the fans are running at the correct speed and the key switch is turned on the Merlin 1500S will open the gas valve and the green Gas On LED will illuminate ON Gas On OFF Ga...

Page 8: ...Under normal working conditions this LED is off If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal wo...

Page 9: ...l pressure differential switch or current switch VOLT FREE INPUT 9 BMS OUT contacts Normally Closed Common and Normally Open 10 PRESSURE SENSOR Disabled 11 EM REMOTE Remote EM Stop buttons and Fire Al...

Page 10: ...Merlin 1500S User Guide Rev 07 05 19 10...

Page 11: ...Merlin 1500S User Guide Rev 07 05 19 11...

Page 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...