Installation & Operation Manual                                                                                              Merlin WLDZ4 

 

 

Rev: 2   02-24

 

 

   Auto Reset Switch

 

 
The panel has a built-in auto reset feature. There is a dipswitch located on the circuit board labelled [AUTO RESET].  

This is factory set in the ‘Off’ position i.e. 

when power is restored after a power cut or loss, the panel has to be 

restarted manually. When enabled, the system will restart automatically when power is restored.  
 

AUTO SWITCH 

CONDITION 

OFF 

Panel has to be restarted manually following a power cut/loss and/or alarm. 

ON 

Panel will automatically restart when power is restored. 

 

   Zone 1 - 4 Set-Up Switches

 

 
There are dipswitches located on the WLMZ4 circuit board labelled [ZONE 1] and [ZONE 2]. 

This is factory set in the ‘Off’ position. For each of the 

water detection zones you are using please ensure that the 

relevant zone has being enabled. The zone you are not using should be left disabled.  

 

ZONE 1/2/3/4 SWITCH 

CONDITION 

OFF 

Water leak detection zone disabled. 

ON 

Water leak detection zone enabled. 

 

   Factory Set Condition 

 

SWITCH 

CONDITION 

BMS 

OFF 

AUTO RESET 

OFF 

ZONE 1 

OFF 

ZONE 2 

OFF 

ZONE 3 

OFF 

ZONE 4 

OFF 

 

   Trouble Shooting 

 

Fault. 

Possible Cause/Correction. 

Water Leak Monitor not responding. 

o

 

Incorrect wiring 

o

 

Zone switches not properly configured 

WLMZ4 Panel not responding. 

o

 

Incorrect Wiring 

o

 

No Power 

o

 

Auto-Reset not properly configured 

 
 

Operation 

   Initial Power-Up (Commissioning) 

 

On connecting mains power, press reset to start. The system will close the solenoid valve when an emergency stop 
has been pressed, water leak has been detected or any alarm signal has been triggered. 
When the system is connected to the mains power supply, the Power LED will illuminate RED.  

 
 
 

Summary of Contents for MERLIN WLMZ4

Page 1: ...tion panels which can be used in many applications such as factories server rooms shopping centres and boiler houses The WLMZ4 is used with up to six 6 Water Leak Monitors in a single cable run for de...

Page 2: ...on Location Positioning 4 Access Mounting 4 Internal Board Overview 4 Board Connections Overview 5 Wiring your Detector 5 BMS Switch 5 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condit...

Page 3: ...the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or other causes not arising from defects in material or workman...

Page 4: ...and ensure the wall surface is flat to prevent base distortion After executing the mounting and the connections replace the front cover and insert the security caps over the four bolts Access to the i...

Page 5: ...he water supply is on off and used in conjunction with the 24vdc output and other external relays that affect other devices and controls such as purge fans and audible alarms etc SOUNDER STROBE 24vdc...

Page 6: ...e water detection zones you are using please ensure that the relevant zone has being enabled The zone you are not using should be left disabled ZONE 1 2 3 4 SWITCH CONDITION OFF Water leak detection z...

Page 7: ...s used to mute the sounder inside the board when in alarm The internal buzzer operates at approximately 60db measured 30cm 1ft from a closed panel RESET The reset button is located on the front fascia...

Page 8: ...at may be found in the content of this document For information not covered in this document or if there is a requirement to send comments corrections please contact S S Northern using the contact det...

Reviews: