background image

Installation & Operation Manual                                                                                              Merlin WLDZ4 

 

 

Rev: 2   02-24

 

 

   Board Connections Overview 

 

POWER/LINE IN 

100-240vac mains power is supplied to the [POWER/LINE IN]

 

connector using a 3-core cable fused 

at 3A. On connecting the mains supply to the panel the power LED indicator will light up 

 this is located on the 

front.

 

 

WATER VALVE 

100-240vac electrical power output from the [VALVE OUT] terminal using a 3-core cable to a water 

solenoid valve, which can shut the water supply on alarm status. 

 

 

WATER LEAK MONITOR (Zones 1 

 4)

 24vdc power supply to Water Leak Monitors are wired to [DETECTOR 

ZONE] terminals. For more information, see section

Wiring your detector. 

 

GENERAL ALARM 

An open/close input for external alarm (i.e. remote emergency shut-off buttons). 

 

 

BMS OUTPUT 

Connections are available on the board for Building Management Systems. These are volt free 

connections.

 

This is a relay that changes state in alarm or when the water supply is on/off and used in conjunction 

with the 24vdc output and other external relays that affect other devices and controls such as purge fans and 
audible alarms etc.

 

 

SOUNDER-STROBE 

24vdc output for an external sounder alarm/ strobe lighting to activate on alarm.

 

 

 

   

Wiring your Detector 

 

 

Power is supplied to a WLM via the [PANEL] terminal [+ / -] and using the WLMZ4 panel [DETECTION ZONE] 
terminal.  
If you are using a WLMZ4 panel you will need to use the detector [C/L]

 

terminal as an alarm relay. 

 

 
 

   BMS Switch

 

 

The WLMZ4 can be integrated with a BMS to make or break a circuit on water supply on/off, (valve open or valve 

closed). This will tell the BMS whether or not electrical power is being sent to the solenoid. There is a dip-switch 
located on the WLMZ4 

circuit board labelled [BMS]. This is factory set to ‘OFF’ position which signals the BMS on 

water supply on/water supply 

off. When switched to ‘ON’, the 

WLMZ4 will only signal the BMS on an alarm, i.e. 

water leak detected, EM Stop pressed, etc.  
 

BMS SWITCH 

BMS SIGNAL 

OFF 

Water supply on or off only. 

ON 

Error condition i.e. water leak detected, emergency stop pressed. 

 
 

Summary of Contents for MERLIN WLMZ4

Page 1: ...tion panels which can be used in many applications such as factories server rooms shopping centres and boiler houses The WLMZ4 is used with up to six 6 Water Leak Monitors in a single cable run for de...

Page 2: ...on Location Positioning 4 Access Mounting 4 Internal Board Overview 4 Board Connections Overview 5 Wiring your Detector 5 BMS Switch 5 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condit...

Page 3: ...the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or other causes not arising from defects in material or workman...

Page 4: ...and ensure the wall surface is flat to prevent base distortion After executing the mounting and the connections replace the front cover and insert the security caps over the four bolts Access to the i...

Page 5: ...he water supply is on off and used in conjunction with the 24vdc output and other external relays that affect other devices and controls such as purge fans and audible alarms etc SOUNDER STROBE 24vdc...

Page 6: ...e water detection zones you are using please ensure that the relevant zone has being enabled The zone you are not using should be left disabled ZONE 1 2 3 4 SWITCH CONDITION OFF Water leak detection z...

Page 7: ...s used to mute the sounder inside the board when in alarm The internal buzzer operates at approximately 60db measured 30cm 1ft from a closed panel RESET The reset button is located on the front fascia...

Page 8: ...at may be found in the content of this document For information not covered in this document or if there is a requirement to send comments corrections please contact S S Northern using the contact det...

Reviews: