Installation & Operation Manual                                                                                              Merlin WLDZ4 

 

 

Rev: 2   02-24

 

 

Installation 

   Typical Application, Location & Positioning 

 
The Merlin WLMZ4 is a 4-zone water detection panel which can be used in many applications such as factories, 
shopping centres, boiler houses and most commonly 

 server rooms. It can be used with up to 12 Merlin Water Leak 

Detection Monitors (3 monitors per zone terminal) for detecting water leaks.  
The controller panel can be integrated with, but not limited to, a BMS (building management system), external 
alarms and remote emergency shut-off buttons.  
 
The control panel should be located in an accessible area for both status observation and alarm purposes.  
 

   Access & Mounting 

 

Unpack all the parts! 
Designed for surface mounting, it must be installed by a licensed, insured contractor or competent person. 

 

Carefully remove the front cover from the unit by unscrewing the four 
bolts located at each corner. To do this 

 use the socket wrench 

provided. Mark the four screw holes located on the back of the 
enclosure to the wall and ensure the wall surface is flat to prevent base 
distortion. 

 
After executing the mounting and the connections 

 replace the front 

cover and insert the security caps over the four bolts. 

 

 

 

Access to the interior of the panel, when carrying out any work, must be conducted by a competent person. 
Before carrying out any work ensure local regulations and site procedures are followed. 
We recommend all Merlin water detection equipment and systems are commissioned by a competent/trained 
engineer to ensure correct installation and operation. Contact S&S Northern for more information. 

 

   Internal Board Overview 

 

 

1.

 

100-240VAC Mains power Input 

2.

 

100-240VAC Water Solenoid Valve Output.  

3.

 

24VDC Water Leak Monitors Supply (Zone 1)  

4.

 

24VDC Water Leak Monitors Supply (zone 2)  

5.

 

24VDC Water Leak Monitors Supply (Zone 3)  

6.

 

24VDC Water Leak Monitors Supply (zone 4)  

7.

 

General Alarm input 

8.

 

NOT USED 

9.

 

NOT USED 

10.

 

BMS output contacts 

11.

 

24VDC Sounder/ Strobe alarm  

12.

 

Switch - BMS Selection & Auto Reset  

13.

 

Switch - Zone 1/2/3/4 enable/disable  

 
 

Note:

 Terminal blocks are plug/socket type and may be removed to ease wiring.  

 

 

 

 

Be careful when creating access for cables 

 Damage to circuit boards will void any warranty! 

 

Water leak Monitors are sold separately.

 

Summary of Contents for MERLIN WLMZ4

Page 1: ...tion panels which can be used in many applications such as factories server rooms shopping centres and boiler houses The WLMZ4 is used with up to six 6 Water Leak Monitors in a single cable run for de...

Page 2: ...on Location Positioning 4 Access Mounting 4 Internal Board Overview 4 Board Connections Overview 5 Wiring your Detector 5 BMS Switch 5 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condit...

Page 3: ...the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or other causes not arising from defects in material or workman...

Page 4: ...and ensure the wall surface is flat to prevent base distortion After executing the mounting and the connections replace the front cover and insert the security caps over the four bolts Access to the i...

Page 5: ...he water supply is on off and used in conjunction with the 24vdc output and other external relays that affect other devices and controls such as purge fans and audible alarms etc SOUNDER STROBE 24vdc...

Page 6: ...e water detection zones you are using please ensure that the relevant zone has being enabled The zone you are not using should be left disabled ZONE 1 2 3 4 SWITCH CONDITION OFF Water leak detection z...

Page 7: ...s used to mute the sounder inside the board when in alarm The internal buzzer operates at approximately 60db measured 30cm 1ft from a closed panel RESET The reset button is located on the front fascia...

Page 8: ...at may be found in the content of this document For information not covered in this document or if there is a requirement to send comments corrections please contact S S Northern using the contact det...

Reviews: