Installation & Operation Manual                                                                                               Merlin GDP4 

 

 

Rev: 11   03-21

 

5  

   Internal Board Overview 

 

 

1.

 

100-240VAC Mains power Input 

2.

 

100-240VAC Gas Solenoid Valve Output.  

3.

 

24VDC Gas detector power supply (Zone 1)  

4.

 

24VDC Gas detector power supply (zone 2)  

5.

 

24VDC Gas detector power supply (zone 3)  

6.

 

24VDC Gas detector power supply (zone 4) 

 

7.

 

Remote emergency stop buttons  

8.

 

Heat Sensor: Fusible Links 

9.

 

Fire panel connection  

10.

 

BMS output contacts.  

11.

 

24VDC Sounder/ Strobe alarm  

12.

 

Switch - BMS Selection & Auto Reset  

13.

 

Switch - Zone 1, 2, 3 & 4 enable/disable  

 
 
 

Note: Terminal blocks are plug/socket type and may be removed to ease wiring. 

 

 

 

 

Be careful when creating access for cables – Damage to circuit boards will void any warranty! 

 

Detectors are sold separately and shipped pre-calibrated and configured!

 

 

   Board Connections Overview 

 

POWER/LINE IN 100-240vac mains power is supplied to the [POWER/LINE IN] connector using a 3-core cable fused 
at 3A. On connecting the mains supply to the panel the power LED indicator will light up – this is located on the 
front. 

 

GAS VALVE 100-240vac electrical power output from the [VALVE OUT] terminal using a 3-core cable to a gas 
solenoid valve, which can shut the gas supply on alarm status.  
 
GAS DETECTOR (Zones 1 – 4) 24vdc power supply to gas detectors are wired to [GAS DETECTOR ZONE] 
terminals. For more information, see sectionWiring your detector. 

 

EM REMOTE An open/close switch for remote emergency shut-off buttons detailed on the circuit board as [EM 
STOP].  

 

HEAT SENSOR An open/close switch for heat sensors/ thermal links detailed as [HEAT SENSOR].  

 

FIRE PANEL An open/close switch for fire alarms detailed on the circuit board as [FIRE PANEL].  

 

BMS OUTPUT Connections are available on the board for Building Management Systems. These are volt free 
connections. This is a relay that changes state in alarm or when the gas is on/off and used in conjunction with the 
24vdc output and other external relays that affect other devices and controls such as purge fans and audible alarms 
etc. 

 

SOUNDER-STROBE 24vdc output for an external sounder alarm/ strobe lighting to activate on alarm. 

 
 

 

 

Summary of Contents for Merlin GDP4

Page 1: ...be used in many applications such as factories car parks shopping centres and boiler houses The GDP4 is used with up to twelve 12 gas detectors in a single cable run for monitoring and detecting gas i...

Page 2: ...ew 5 Board Connections Overview 5 Wiring your Detector 6 BMS Switch 6 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condition 7 Trouble Shooting 7 Operation 7 Initial Power Up Commissioni...

Page 3: ...of defects in material and workmanship for a period of three 3 years from date of purchase or one 1 years for oxygen detectors The manufacturer s liability hereunder is limited to replacement of the p...

Page 4: ...s Methane NG High Level 300mm 1ft from ceiling Liquid Petroleum Gas LPG Low Level 300mm 1ft from ground level Carbon Monoxide CO Breathing Zone 1700mm 5ft 6 from ground level Hydrogen H High Level 300...

Page 5: ...supply to the panel the power LED indicator will light up this is located on the front GAS VALVE 100 240vac electrical power output from the VALVE OUT terminal using a 3 core cable to a gas solenoid...

Page 6: ...top pressed Auto Reset Switch The panel has a built in auto reset feature There is a dipswitch located on the circuit board labelled AUTO RESET This is factory set in the Off position i e when power i...

Page 7: ...light up Gas On On start up the Gas on LED will flash for one minute to check for gas detected If no gas detected or any other faults the gas valve will open and the Gas On LED will illuminate GREEN G...

Page 8: ...es tetraethyl lead halogens and halogenated compounds Manual Circuit Simulation Test When the test button on the circuit board is pressed and held for 3s the detector will simulate an open circuit to...

Page 9: ...Nitrogen 60s All certified test gases supplied by S S Northern are classified as non flammable and non toxic however they do contain gas under pressure and may explode if heated to extreme temperatur...

Page 10: ...Safe Areas not to be used in potentially explosive atmospheres Indicators LED Mounting Wall Mounting Electrical Max Power Consumption 20W Max Full Load Power Voltage Input Range 100 240vac Gas Valve...

Page 11: ...Installation Operation Manual Merlin GDP4 Rev 11 03 21 11 Page intentionally left blank...

Page 12: ...en damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or...

Reviews: