This is factory set in the ‘off’ position which instructs the system to shut down the  

   

fan(s) and gas supply on activation of the Emergency shut off button(s). On  

   

   

installation, this can be switched to the ‘on’ position if required. This will instruct the  

   

system to leave the fans on and only shut off the gas supply on activation of the  

   

Emergency shut off button(s). Note: This option is not available if Fan Switch is not  

   

installed. 

 

3.7 

Gas fill and prove time 

Gas fill and prove times are adjustable. There are two dip-switches located on the  

  

inside facia of the Merlin  

labelled “Fill Time” and “Prove Time”. They are  

  

factory set in the ‘off’ position. Fill and prove time can be changed by turning the relevant dip 
switch to on position.  

 Fill time: Off 

– 5 secs, On – 10 secs  

Prove time: Off 

– 30 secs, On – 50 secs  

 Once the settings has been changed, please remove power from the fuse spur for 10     

seconds. 

3.8 

Auto reset 

The Merlin  has a built-in auto reset feature. There is a dip-switch located on the 

inside facia of the Merlin  

labelled “Auto Reset”. This is factory set in the ‘off’ 

position. When the power is restored after the power cut, the panel has to be restarted 
manually. On installation

, this can be switched to the ‘on’ position if required. This will instruct 

the system to restart automatically when power is restored after the power cut.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for Merlin 1000VW+

Page 1: ...Merlin 1000VW Product Data Sheet S S Northern Ltd 1 Gas Safety Products Merlin 1000VW Gas Proving Electric Water Isolation System Installation operating and maintenance 20 01 2017...

Page 2: ...as Detected 4 2 11 FS 123 4 2 12 Fan PD Switch 4 2 13 12v DC 4 2 14 Internal Buzzer 4 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 Power LED 4 Gas...

Page 3: ...ally fused at 3 Amps 2 4 Electric Contactor An electrical output will be supplied to an electrical contactor supplied by others This will be internally fused at 3 Amps and should be connected to the t...

Page 4: ...the fans when the control panel is switched on 2 12 Fan PD Switch This terminal is used to receive an input signal from external air pressure switches or external current monitors This terminal is li...

Page 5: ...panel is checking the integrity of the gas installation upon start up GREEN proving the gas line do NOT operate any appliances Test Fail LED Under normal working conditions this LED is off When the p...

Page 6: ...MS integration The Merlin 1000VW can be integrated with a BMS to make or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the room has use of the gas...

Page 7: ...acia of the Merlin 1000VW labelled Fill Time and Prove Time They are factory set in the off position Fill and prove time can be changed by turning the relevant dip switch to on position Fill time Off...

Page 8: ...ns and Fire Alarm input wired in series purchased separately VOLT FREE INPUT 10 Methane CO or LPG Detector power supply and volt free input purchased separately CO2 Monitor purchased separately VOLT F...

Page 9: ...ww snsnorthern com info snsnorthern com South East Division Tel 44 0 1702 291 725 Fax 44 0 1702 299 148 south snsnorthern com Rev Date Author Description 01 20 01 2017 S S Northern BT Merlin 1000VW Pr...

Reviews: