S&S Northern Merlin 1000VW+ Installation, Operating And Maintenance Download Page 6

Merlin 

 

  

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

S&S Northern Ltd

  

6  

 

CO2/Gas Detected LED  

Under normal working conditions this LED is off. If the external Merlin detector/ CO2 

connected detects gas this will show RED and the Gas valve will turn off. 

OFF = OK  

RED = Gas detected / high ppm levels of CO2 

 

 

Fan Fault LED 

Under normal working conditions this LED is off. If a fan fault is present for more than 10 

seconds, the LED will illuminate RED. The system will only go into fan fault from gas on.

 

OFF = OK  

RED = the gas supply has been shut off due to a ventilation fault.  

WHEN A FAULT IS PRESENT YOU WILL NEED TO CONTACT YOUR 

SERVICE/MAINTENANCE COMPANY. 

 

YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR OR RECTIFY THE FAULTS 

UNLESS YOU ARE QUALIFIED TO DO SO.  

 

3.3 

Using the emergency shut off  

The Emergency shut off button is located on the front of the panel. There is also a facility for 

remote shut off buttons to be wired in series.  

The Emergency shut off button(s) will cut off the gas supply when activated.  

To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel 

restarted.  

 

3.4 

BMS integration 

The Merlin  can be integrated with a BMS to make or break a circuit on gas on/gas 

off, (valve open or valve closed). This will tell the BMS whether or not the room has use of the 
gas supply.  

There is a dip-switch located on the inside facia of the Merlin  

labelled ‘BMS 

Selection’. This is factory set in the ‘off’ position which signals the BMS on gas on/gas off. 
When swit

ched to the ‘on’ position, the  will only signal the BMS on a fault, i.e. CO2 

high level detected, gas detected, EM Stop pressed, etc.  

 

3.5 

 Fire alarm integration  

               The Merlin  can be integrated with a fire alarm to close the gas supply      

               automatically in the event of a fire.  

               The volt free fire alarm signal can be wired in series with any remote emergency shut   

               off buttons. If there is no remote emergency stop buttons installed wire this directly to  
               

the terminal marked ‘EM REMOTE’ 

 

3.6 

 Fan switch integration  

  

   There is the facility to connect a Fan Switch (FS1 or FS2 sold separately). 

  

   The Fan Switch provides the facility to turn on the fan(s) when the key switch on the 

 

   Merlin  is in the on position and turn the power off to the fan(s) when the    

 

   key switch on the Merlin  is in the off position. There is a dip-switch located 

 

   inside the facia of the Merlin  labelled EM Selection. 

Summary of Contents for Merlin 1000VW+

Page 1: ...Merlin 1000VW Product Data Sheet S S Northern Ltd 1 Gas Safety Products Merlin 1000VW Gas Proving Electric Water Isolation System Installation operating and maintenance 20 01 2017...

Page 2: ...as Detected 4 2 11 FS 123 4 2 12 Fan PD Switch 4 2 13 12v DC 4 2 14 Internal Buzzer 4 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 Power LED 4 Gas...

Page 3: ...ally fused at 3 Amps 2 4 Electric Contactor An electrical output will be supplied to an electrical contactor supplied by others This will be internally fused at 3 Amps and should be connected to the t...

Page 4: ...the fans when the control panel is switched on 2 12 Fan PD Switch This terminal is used to receive an input signal from external air pressure switches or external current monitors This terminal is li...

Page 5: ...panel is checking the integrity of the gas installation upon start up GREEN proving the gas line do NOT operate any appliances Test Fail LED Under normal working conditions this LED is off When the p...

Page 6: ...MS integration The Merlin 1000VW can be integrated with a BMS to make or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the room has use of the gas...

Page 7: ...acia of the Merlin 1000VW labelled Fill Time and Prove Time They are factory set in the off position Fill and prove time can be changed by turning the relevant dip switch to on position Fill time Off...

Page 8: ...ns and Fire Alarm input wired in series purchased separately VOLT FREE INPUT 10 Methane CO or LPG Detector power supply and volt free input purchased separately CO2 Monitor purchased separately VOLT F...

Page 9: ...ww snsnorthern com info snsnorthern com South East Division Tel 44 0 1702 291 725 Fax 44 0 1702 299 148 south snsnorthern com Rev Date Author Description 01 20 01 2017 S S Northern BT Merlin 1000VW Pr...

Reviews: