background image

26

 

5.2.10.2 ESU WATER HEATER OR ESUCH WATER COOLER CONTROL UNIT

 

The ESU or ESUCH unit must be ordered as a separate item because they are not included with the unit.

 

The mixing control unit is used to control the flow or temperature of heating (cooling) water to the water heaters/coolers. The ESU unit regulates 
the heating water temperature at the inlet to the water heater by mixing the inlet water and return line, the ESUCH unit regulates the flow of 
cooling water to the water cooler at a constant cooling water inlet temperature. (The designation xx in the type symbol indicates the type of 
pump, indicates the Kv value of the mixing valve). The control is provided by a BELIMO servomotor. For control units in conjunction with Digireg

®

 

control, it is necessary to use the design B, which features a three-point actuator, designed for control by a Digireg

®

 controller. 

I

n addition to

power regulation, the control system also provides protection of the water heater against freezing by means of the ESU unit. The water flowing 
through the unit may not contain impurities, solid admixtures and aggressive chemicals that damage copper, brass, stainless steel, zinc, plastics, 
rubber. The highest permitted operating parameters of the heating water are as follows:

 

 

 

 

Maximum water tempe110 °C 
Maximum water pressure 1 MPa 
Minimum water pressure 20 kPa

 

The water temperature must not fall below the ambient air temperature during operation, as there is a risk of condensation in the pump motor. 
The minimum operating water pressure ensures that no air is sucked in by the vent valve, which must be mounted at the highest point of the 
water circuit. For the ESUCH unit, it is always necessary to install insulation against condensation of air humidity on the surface of the node on 
the entire node (suitable material is e.g. Armaflex).

 

Layout diagram of ESU node components

 

Layout diagram of ESUCH components:

 

Cold water 

exchanger

 

hot-water 

exchanger

 

The mixing unit is connected to the heater or cooler. The mixing unit must never be loaded by tension and twisting of the connected piping. 
Mixing units should be mounted on separate hinges using heating sleeves on the wall, pipes or on an auxiliary structure. When placed under the 
ceiling, it is necessary to maintain control and service access to the mixing unit for easy cable connection and service access. The filter requires 
regular inspection, maintenance and cleaning. 

When assembling the node, it is necessary to turn the filter downwards with the sludge pan. 

If the position is incorrect, there is a risk of increased clogging/choking of the filter. Reduced throughput or even impermeability of the 
filter results in a significant reduction in heater performance and increases the risk of the heater freezing. 

Especially during the test 

operation, it is necessary to check and clean the sludge pan.

 

If the filter is often clogged, the entire heating circuit must be cleaned. Even during normal operation of the device, it is necessary to check the 
filter regularly. When cleaning the filter, all water lines must be closed to minimize water leakage from the system. Always install the mixing unit 
so that air can escape to the heater vent points or the boiler circuit vent points. The mixing unit must be fixed so that the pump motor shaft is in a 
horizontal position. After flooding the system, the circulation pump must be bled according to the manufacturer's instructions

.

 When connecting

the mixing unit, it is necessary to check the correct setting of the valve and actuator. With an assembled mixing unit, the position of the inner 
segment of the mixer can be identified by the shoulder on the front of the shaft extension. The perpendicular line to the mounting surface at the 
three-way valve points to the axis of the inner segment. For the version with a three-way valve, proceed as follows. Of the three paths, the valve 
always has the path to which the bevelled surface on the valve shaft points. With an assembled mixing unit, the setting can be identified by the 
notch on the face of the shaft extension. The notch always points to a closed water line - see following image.

 

Heating 

Mixing 

Cooling 

Splitting 

www.solerpalau.co.uk

 

CAUTION!

 

The design of a suitable mixing unit must be 
individually adapted to the conditions of the

 

application in order to ensure sufficient 
valve authority!

 

Summary of Contents for DUOVENT COMPACT DV

Page 1: ...INSTRUCTION MANUAL www solerpalau co uk DUOVENT COMPACT DV Ventilation unit with heat recovery...

Page 2: ...n Connection of electric heater Connection of water heater Connection of water cooler Connection of direct evaporator Connection of condensate drain Bypass and mixing flap Inlet and outlet flap 5 2 10...

Page 3: ...ation Warranty conditions The device must be installed by a professional air handling service company DUOVENT COMPACTDV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by t...

Page 4: ...hat could affect safety and proper function are prohibited Installation and operating documentation must be available to the operator and service It is advisable to place it close to the installed uni...

Page 5: ...nit for ventilation of pool halls Order examples DUOVENT COMPACT DV 3000 DI DX MX KL G4 F7 F7 DVAV JH2 Unit size 3000 with electric heater direct evaporator bypass and mixing flap two stage filtration...

Page 6: ...INSULATION OF THE ANTIFREEZE PROTECTION CONTACT SENSOR WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNI...

Page 7: ...0 182 DUOVENT DV 1200 521 992 312 80 2091 260 5 260 5 582 300 500 DUOVENT COMPACT DV 500 to 1200 under ceiling arrangement positions xH AH unit position drawn UNIT BOTTOM VIEW Exchanger outlets UNIT T...

Page 8: ...2 X3 L Y D Y Exchanger outlets D 20 D 1 2 1 2 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 19 18 18 18 Condensate drains 152 152 152 21 www solerpalau co uk 40 A 150 B A B 150 F 157 42 42 X1 X...

Page 9: ...94 694 694 627 627 694 694 694 694 694 1085 1085 1085 1085 1085 1085 1085 DUOVENT COMPACT DV 1800 to 7800 floor arrangement positions xP AP unit position drawn X3 X1 X2 X E E X 1 2 1 2 19 18 18 18 Tra...

Page 10: ...00V 50Hz 3000 1238 927 1 8 1 4 89 1 3500 320 387 3000 DCA DCC 3000 DCA DX 21 8 21 8 21 3 21 3000 DI 15 22 4200 4200 DCA 4200 DCB 4200 DCA DCC 4200 DCA DX 4200 DI 29 8 22 30 2 20 5 29 8 3 400V 50Hz 420...

Page 11: ...ES EXCHANGER OUTLETS ETC Ensure proper balancing of the transported unit The ropes above the unit must be stretched to prevent damage The outdoor variants of the units are fitted with transport profil...

Page 12: ...is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate formed in the air duct can in unfavourable conditions spill into the interior of the unit where...

Page 13: ...tion box 5 1 2 HOW TO STORE THE UNIT AT THE DESTINATION The unit is designed for floor mounting in a vertical position positions marked xV in the unit code or horizontal position positions marked xP i...

Page 14: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with...

Page 15: ...let and outlet ports with respect to the position of the exchanger connection pipes Neck variants vertical arrangement viewed from unit operation side INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INL...

Page 16: ...TLET OUTLET www solerpalau co uk INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET...

Page 17: ...INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET...

Page 18: ...n it is exceeded the operating thermostat opens and switches off the heater after cooling below 60 C the heater automatically switches on again Location of the release button under the cover on the un...

Page 19: ...nger connections it is necessary for example to hold the heat exchanger neck with a second wrench so that the tightening torque is not transmitted to the heat exchanger body Table of dimensions of wat...

Page 20: ...n screws on the heat exchanger collectors The heat exchanger can then be disconnected from the heating water distribution system and removed from the unit Max operating water temperature of water heat...

Page 21: ...the cooler must be vented after connecting and filling the system with cooling water The vent screws are located directly at the heat exchanger connection necks The vent screws are accessible either...

Page 22: ...specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a technician with the appropriate authorization according to the law 5 2...

Page 23: ...ING FLAP In the basic version each unit is equipped with a bypass flap of the plate heat exchanger BP The bypass is used for summer ventilation defrost control of the recuperation exchanger in the eve...

Page 24: ...on mode Location of mixing and bypass flap for DUOVENT 500 800 1200 units with MX mixing mode www solerpalau co uk ETA flap Mixing flap MX ODA flap Bypass flap BP Circulation flap C part 1 ODA flap Ci...

Page 25: ...uators 5 2 10 BASIC ACCESSORIES 5 2 10 1 CONDENSATE DRAIN TRAPS Condensate traps must be ordered as a separate item as they are not included with the unit Vacuum type siphon scheme SF P 300 bottom edg...

Page 26: ...ected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When placed under the ceiling it is necessary to maintain control an...

Page 27: ...I C control system to the electrical distribution network is made by a separate supply cable which is not part of the delivery of the device www solerpalau co uk Ventilation unit with heat recovery DU...

Page 28: ...ts according to the set parameters in the automatic summer winter mode according to the outdoor temperature and time dependencies Manual mode selection is also possible The heater can be hot water con...

Page 29: ...otation of the fans the correct phasing of the damper actuators and mixing valves If the unit is equipped with a Digireg control system directly from the factory a SETPACK test package has been perfor...

Page 30: ...onnection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATION The material content of the comprehe...

Page 31: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with t...

Page 32: ...NH IH2 JH2 MH2 NH2 263 295 263 365 KH LH OH PH KH2 LH2 OH2 PH2 263 295 263 295 1200 1200 all positions 420 365 365 420 ETA filter size ETA mm ODA filter size ETA mm Size of DUOVENT DV Vnom m3 h Neck...

Page 33: ...replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove the fan as shown in the following figure K...

Page 34: ...nitor the implementation of the measures taken Check the siphons for condensate drainage especially their permeability and tightness especially the tightness of the mounting on the unit and the tightn...

Page 35: ...l applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be a...

Reviews: