![S&P CAB ECOWATT PLUS Manual Download Page 59](http://html1.mh-extra.com/html/sandp/cab-ecowatt-plus/cab-ecowatt-plus_manual_3102488059.webp)
EN
59
7.2. PROGRAMMING
IMPORTANT:
Before starting programming, it is important to select the appropriate operation mode. Check point 6.6.1. Change
operation mode of this manual and choose one of these modes:
PI PRESS+RTC, PI RTC, PRTC or MIN-
MAX+RTC.
During programming process must defi ne following parameters:
•
T1, T2, T3:
Start time for each period frame (OFF,00:00-23:59).
•
Period T1, Period T2, Period T3:
Minutes of each time period related to start time defi ned (until 480 minutes).
•
Set point T1, Set point T2, Set point T3:
Set point in % during period frame over operation mode previously selected
(e.g. if
PI PRTC mode is selected and set point T1 is 50%, during period frame the fan will reduce the speed accordingly
with a minus 50% of the pressure set point defi ned SC).
Example:
MONDAY
TUESDAY
…
SATURDAY
SUNDAY
1:00
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
2:00
3:00
4:00
5:00
6:00
7:00
8:00
T1 = 60min
SetpointT1 = 50%
T1 = 60min
SetpointT1 = 50%
9:00
T2 = 120 min
SetpointT1 = 50%
T2 = 120 min
SetpointT1 = 50%
10:00
T1 = 60min
SetpointT1 = 50%
T1 = 60min
SetpointT1 = 50%
11:00
12:00
13:00
14:00
T2 = 120 min
SetpointT1 = 50%
T2 = 120 min
SetpointT1 = 50%
15:00
16:00
22:00
23:00
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
T3 = 480 min
SetpointT3 = 25%
0:00
When one of these modes is selected, start programming with following sequence:
30
DATE:
14/01/15
Date introduction
Increase / Decrease value
Forward / Back
+
3
”
Press for 3 seconds
HOUR:
12:28
Time introduction
OK
OK
OK
OK