To change the fan-channel number should follow these steps:
• Check that ON/OFF switch is in “0” position
• Access to the internal board and position the micro switch SW2-2 in “ON”
• Connect the PROSYS ECOWATT console to the internal board using J9 connector
• Turn on the device using the ON/OFF switch
• Select the desired language on the fi rst screen
• Proceed as follows:
ENTER PASSWORD:
1 1 1 OK
+
CHANGE PASSWORD?
NO
YES
3”
SETUP MENU
CAHNNEL N:1 OK
OK
OK
OK
OK
OK
FACTORY SETTING?
NO YES
OK
MODE
<PI PRESSURE OK
OK
OK
NO
NO
NO
NO
MIN-OUTPUT
< 20%
OK
OK
OK
Press simultaneously for 3”
Enter the password
Default: 1 1 1
It is possible to assign a new password to your device
Selec on on which cannel you want to set the fan
Press on “NO” to do not return to Factory se ng
Press on “OK”
Press on “OK”