Instructions for the installer, maintenance
technician and final user
Page 41 of 54
© SandenVendo Europe SpA
4.2.5.1.3 Displaying and setting the set point
Press
SET
for more than 1 second to display the set point;
Increase or decrease the set point using the
▲
or
▼
buttons respectively, until reaching the
desired value;
Press
SET
again to confirm the new value.
4.2.5.1.4 Errors List
ERRORS
DESCRIPTION
ES
The compressor has a timing delay when starting, therefore the LED
of the compressor on the display starts to flash.
E0
Still or flashing means an adjusting probe error:
• probe not working, the probe signal is interrupted or in short circuit:
• probe is not compatible with the instrument;
The E0 alarm signal is stable if it is the only alarm present (the
temperature value is no longer shown), it flashes if there are other
alarms or if the second probe is shown
E1
Flashes evaporator probe error:
• probe not working, the probe signal is interrupted or in short circuit;
• probe is not compatible with the instrument;
EE
Visualized during functioning or activation
Error in reading of the machine parameters. See memorised data
errors.
EF
Visualized during functioning or activation
Error in reading of the working parameters. See memorised data
errors.
ED
The last defrosting finishes when exceeding the maximum time.
The indication disappears if the next defrost is finished correctly.
DF
Defrosting in course:
• it is not an alarm signal but an indication that the instrument is doing
a defrosting.
AFR
Antifreeze Alarm
• When AFR flashing on the display the glycol pump is broken or the
glycol circuit is empty
DISPLAY
BLINKS
The control unit display and all the LED's are flashing:
• indicates that the door is open, or that the door switch is not working
correctly
• it is activated when the door remains open for more than one hours