80 S&C Instruction Sheet 461-504
Using TripSaver
®
II Service Center Confi guration Software Version 1.8
Current, A.
This indicates the current level (defi ned here) of each event shown in the
“Tripped On” column, in primary amperes. See Figure 113.
Figure 113. The column displaying current level for each event.
•
For Overcurrent (TCC0, TCC1, TCC2, TCC3, and the NR curves):
This indicates
the value of the current measured just before the vacuum interrupter contacts opened.
•
For Overload:
This indicates the value of the current measured just before the vacuum
interrupter contacts opened.
•
For Sectionalizer:
This indicates the maximum value of the current measured during
the last sectionalizing event before the enabled
Sectionalizing
feature commanded
the TripSaver II recloser to drop open.
•
For LMO:
This indicates the value of the load current measured just before the vacuum
interrupter contacts opened by the
Local Manual Open
command.
•
For Suspicious:
This indicates the value of the load current measured when a suspi-
cious local manual open attempt was detected.
Clear All Events.
Clicking on this button will clear the log for “Trip Events” in the
connected TripSaver II recloser. This can be useful prior to deploying a TripSaver II
recloser to a different location. This button is grayed out when viewing a snapshot fi le.
Note 1:
The command executes immediately after clicking on the button. Save a snapshot
before clearing the log.
Note 2:
Clicking on this button does not reset the relative timer.
Note 3:
Clicking on this button does not erase anything from the memory used to store
full event logs for use by S&C Technical Support.