28    S&C Instruction Sheet 768-550 

Voltage Sensor

Output Terminals 

on Switch Control

Output Terminals 

on Burden Assembly

Jaw-Side Pole 1

23 and 26

VS01 and N1

Jaw-Side Pole 2

24 and 26

VS02 and N1

Jaw-Side Pole 3

25 and 26

VS03 and N1

Hinge-Side Pole 1

27 and 30

VS04 and N2

Hinge-Side Pole 2

28 and 30

VS05 and N2

Hinge-Side Pole 3

29 and 30

VS06 and N2

▲ 

Switch poles are identified as follows: When facing the mechanism side of 

the switch, Pole 1 is on the left, Pole 2 is in the center, and Pole 3 is on the 
right . For the tiered-outboard configuration, Pole 1 is on the top, Pole 2 is in 
the center, and Pole 3 is on the bottom .

Calibration

Table 3. Voltage Sensor Wiring

Current-sensor magnitude ratios written on this card 

can be used directly to calibrate the current-sensing inputs 
to the RTU.

Refer to the manufacturer’s instructions for calibrating 

the voltage-sensing and current-sensing inputs to the RTU. 
Voltage-sensor and current-sensor phase-angle shifts are not 
generally required for calibrating transducer-equipped RTUs. 
Measure the voltage-sensor output selector switch is in the 

69 Vac

 position after calibrating the RTU.

For future reference, keep the yellow card in the water-

resistant envelope and place it in the instruction manual 
holder inside the control unit enclosure.

S&C Data Sheet 768-93 (furnished) provides additional 

information on the sensors included with S&C Automated 
Switches. Refer to this publication for details regarding 
specifications and accuracies of the outputs. 

Alternate Location of Data

If the yellow card is not available, the magnitude-ratio and 
phase-angle shift measurements of the voltage-sensor portion 
of each S&C Current/Voltage Sensor are also stamped on the 
left side of the sensor’s terminal pad. These measurements 
are expressed in the form  “V XXXX/XX.X,” where the value 
to the left of the “/” is the magnitude ratio and the value to 
the right is the phase-angle shift. 

The magnitude-ratio and phase-angle shift measurements 

of each S&C Current Sensor and the current-sensor portion 
of each S&C Current/Voltage Sensor are also stamped on the 
right side of the sensor’s terminal pad. These measure ments 
are expressed in the form “I XXX.X/X.X,” where the value to 
the left of the “/” is the magnitude ratio and the value to the 
right is the phase-angle shift.

Summary of Contents for Scada-Mate CCU-SP

Page 1: ...nstalling and Connecting a User Supplied Communication Device 13 Connecting an Antenna 14 Connecting a Land Line Interface 14 Connecting Control Power 15 Connecting Remote Terminal Unit Hardware Statu...

Page 2: ...this publication WARNING The equipment in this publication must be selected for a specific application The application must be within the ratings furnished for the selected equipment The warranty and...

Page 3: ...ons including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed If y...

Page 4: ...lace in operation or charge batteries in this equipment G 6226 C WARNING Electrical Shock Before energization and at all times when energized G 6289 D WARNING Electrocution Hazard Failure to follow th...

Page 5: ...stored energy operating mechanism and switch base contain fast moving parts that can severely injure fingers Do not remove or disassemble the operating mechanism or remove access panel on the switch...

Page 6: ...it is packaged and crated appropriately to avoid damage during shipment A catalog drawing and wiring diagram for the communication and control unit is located in a water resistant envelope in the inst...

Page 7: ...auxiliary battery charger float charges extra battery packs needed for some Remote Terminal Units and communication devices Battery charger provides continuous float charge to battery packs Switch co...

Page 8: ...ks provide power for the installation 316L stainless steel NEMA 4X enclosure with three point door latch and padlockable handle Components CCU XP Communication and Control Unit Externally Powered by A...

Page 9: ...bolt of the switch and the top through bolt of the com munication and control unit when using the standard 35 foot 1067 cm control cable is 28 feet 4 inches 864 cm for switches in the upright vertical...

Page 10: ...tach an appropriate lifting sling and slowly raise the sling so it becomes taut Carefully raise the control unit to the mounting height and guide it so the through bolts projecting from the utility po...

Page 11: ...hthecon trolcableplug Secure the plug with the con nector clips Refer to Instruction Sheet 768 500 Retain the dust cover and sensor shorting blocks for future use See Figure 7 STEP 6 Locate the connec...

Page 12: ...ol unit Maintain a 9 inch 229 mm minimum radius when bending the control cable at the drip loop and at the switch connection Adjust the control cable along the length of the utility pole and form a co...

Page 13: ...the communication device See Figure 11 Figure 11 Connect power to the communication device using the indicated termi nal block NOTICE The battery charger float charge is factory calibrat ed to accomm...

Page 14: ...essor When the communication device is supplied by others Prepare a weather tight entrance in the bottom or on the rear of the enclosure in accor dance with utility practice Install the appropri ate s...

Page 15: ...instances the external ac input on the S C Battery Charger is for use only when configuring the remote terminal unit in accordance with the remote terminal unit instructions Refer to the included wiri...

Page 16: ...nished testing functionality of the communication and control unit and the auto mated switch if connected to the communica tion and control unit via the control cable can be accomplished with a person...

Page 17: ...position Then place the battery charger power switch in the On position and confirm that the POWER LED display is lit and the CHARGER OVERVOLTAGE and BATTERY LOW LED displays are not lit When the cont...

Page 18: ...inside the com munication and control unit in the Local mode See Figures 15 and 16 Then press the OPEN or CLOSE pushbutton as required The interrupter OPEN CLOSED indicator on the end of the switch ba...

Page 19: ...ess the interrupter contacts are in the Open posi tion Refer to Instruction Sheet 768 500 S C Scada Mate Switching Systems Outdoor Distribution 14 4 kV through 34 5 kV STEP 4 Provision for tagging the...

Page 20: ...his switch or working on the conductors on either side of the switch test for voltage using proper high voltage test equipment Then install suitable grounding equip ment Failure to observe these preca...

Page 21: ...changes Record the following Battery identification number Date of installation Battery charging voltage Ambient temperature Date removed from service Battery appearance Physical appearance Examine t...

Page 22: ...ry charger switch control typically used in the Type CCU XP does not require recalibration therefore a procedure is not refer enced New Battery Preparation The replacement batteries must be in good co...

Page 23: ...rge the batteries STEP 1 Make sure that the power switch on the bat tery charger is in the Off position STEP 2 Ground the enclosure using the ground lug on the back of the enclosure STEP 3 Place the b...

Page 24: ...For Type CCU SP Place the battery charger in the External Source position Then put the power switch in the Off posi tion b For Type CCU XP Disconnect the fuse block Then after 15 30 seconds discon nec...

Page 25: ...in Plastic Outer Case Manufacturer Hawker Energy Products Type Rechargeable sealed lead starved electrolyte Part Number 0809 0016 S C 9931 267 Nominal Voltage each battery pack 12 Vdc at 25oC 77oF Rat...

Page 26: ...Source 5 hours Dc Output Fuse 10 A 32 V Ac Input Fuse GDC 2A Cyclon Battery Packs in Metal Outer Case Manufacturer Hawker Energy Products Type Rechargeable sealed lead starved electrolyte Part Number...

Page 27: ...ations and the adjusted magnitude ratio used to calibrate the corresponding voltage sensing input to the RTU To determine the adjusted voltage sensor magnitude ratio s measure and record the voltage s...

Page 28: ...ge sensor output selector switch is in the 69 Vac position after calibrating the RTU For future reference keep the yellow card in the water resistant envelope and place it in the instruction manual ho...

Page 29: ...values The corrected sensor ratios may be used by the RTU to adjust the sensor outputs to account for the tolerance variations in the components The magnitude ratio and phase angle shift measurements...

Reviews: