12 S&C Instruction Sheet 768-550
Installation
STEP 7.
A stainless steel security belt is included with the
communication and control unit for pad locking the
connector. Place the security belt around the
connector, between the connector clips and the
enclosure. Insert a padlock (not furnished) through
the security belt holes. See Figure 9.
STEP 8.
Form a drip loop in the control cable where it
attaches to the control unit. Maintain a 9-inch (229-
mm) minimum radius when bending the control
cable at the drip loop and at the switch connection.
Adjust the control cable along the length of the
utility pole and form a coil with any excess cable
(maintain ing a 9-inch (229-mm) minimum radius).
Secure the con trol cable to the utility pole using
suitable guards or clamps.See Figure 10.
Figure 10. Connecting the control cable to the utility pole.
Security belt
Padlock (provided
by others)
Drip loop
(maintain a 9-inch
(229-mm) minimum
radius when bending
the control cable)
Figure 9. Secure the connector at the control unit.
Security belt