S&C Instruction Sheet 665-506
9
Installation
If excess lengths of direct-buried cable are to be fed into the termination compartments
as the unit is lowered, special attention must be paid to the cable position
in the fuse
termination compartments.
Open the doors and secure them with the door holders, to
allow the cable to be fed over the door stiles . Then, as the enclosure is being lowered into
place, feed the cables for connection to the fuse terminals between the horizontal cable
guides, as shown in Figure 5 and the cable-training tag affixed to the enclosure .
NOTICE
To avoid interference with the TransFuser™ Mountings, the cables to be connected
to the fuse terminals must be fed between the horizontal cable guides .
Special cable training is not required in the switch termination compartments .
Make sure all compartment doors open and latch closed without binding .
Figure 5. Cables in fuse-termination compartments must be trained between horizontal cable guides as shown to prevent
interference with operation of the TransFuser Mounting.
TransFuser Mounting (shown in closed position)
rotates to open position for access to isolated,
de-energized fuse
Ground tabs for grounding bushing well inserts
Ground bails are mounted vertically
Cable guides are mounted horizontally, extend
toward TransFuser Mounting