air inlet and 1.5 meters around the air outlet. If the air inlet
and the air outlet are blocked, the cooling ability that the
equipment should have cannot be realized.

Before commissioning

a) Make sure that the water supply pipe of equipment is not
blocked;
b) It is necessary to check the water pipe and the water pump
to confirm that there is a proper amount of water entering the
water pump and exhaust it through the water pump exhaust
valve, otherwise it will cause damage to the water pump;
c) Confirm that the state of the equipment is normal and safe,
otherwise there may be injury and damage.

Gently move the

motor impeller if the

equipment isn’t used

for a long time

For equipment that has not been used for a long time, it may
be difficult to start the pump at the first start. Please gently
move the motor impeller before the equipment is powered on.

The equipment is

forbidden to be

trampled on

Please do not step on or sit on the equipment. Otherwise, it
may cause injury accidents such as falling or overturning

Clean the air filter

regularly

Clean the air filter at least once a week. If it is blocked, the
cooling ability will decrease and the power consumption will
increase, and the alarm will not work properly.

Equipment surface

cleaning

a) Please use cleaning agents that are non-corrosive to
metals and plastics;
b) Please keep the cleaning agent properly after cleaning to
prevent liquid leakage;
c) The container for storing the cleaning agent must be
sealed completely to avoid danger.

No air blowing at the

water outlet

A temp sensor is installed inside the water inlet, and it is
forbidden to blow air inside the device with an air gun.

Wear protective gloves

during maintenance,

inspection and cleaning

a) The sharp edges of the condenser fins may cut the skin;
b)The temperature of the internal compressor and refrigerant
piping is very high, and direct skin contact may cause burns.

Anti-freezing

a) When the ambient temperature is lower than 0

and the

machine is shut down for a long time, it is necessary to drain
the liquid and blow the water away in the system with
compressed air, otherwise there is a danger of freezing and
cracking the components and pipelines.
b) When room temperature is lower than 0

, it is

recommended to use antifreeze with a concentration of not
more than 30% containing ethylene glycol or propylene
glycol.

Summary of Contents for CW-5300

Page 1: ...TY JS 20319 003 1 CW 5300 6000 6100 6200 6260 Industrial Chiller User Manual...

Page 2: ...rly so that you can refer to it whenever you need information This manual is not a quality guarantee Our company reserves the right to the interpretation of the correction of misprint and improperly d...

Page 3: ...4 I Overview 7 II Model Illustration 7 III Product Outlines Parts 8 IV Installation 9 V Operating States Parameters Adjustment 11 VI Alarm Output Terminal 14 VII Maintenance 15 VIII Simple Troublesho...

Page 4: ...on a The power supply must conform to the standard indicated in the nameplate or the manual b Use the standard cable and select the standard wire diameter c The grounding wire must be installed and th...

Page 5: ...ilable Otherwise it may cause anesthesia and suffocation if a large amount of refrigerant fills the enclosed space b Avoid contacting with skin or it will cause frostbite DANGER Failure to take safety...

Page 6: ...r filter at least once a week If it is blocked the cooling ability will decrease and the power consumption will increase and the alarm will not work properly Equipment surface cleaning a Please use cl...

Page 7: ...hiller the refrigerant in the evaporator coil absorbs the heat of the return water and vaporizes into steam The compressor continuously extracts the generated steam from the evaporator and compresses...

Page 8: ...mes are only for one of the models The outlines and parts installation may be slightly different in different models Power Switch Temperature Controller Air Inlet Filter Gauze Water Supply Inlet Elect...

Page 9: ...etc 4 Operating Environment Ambient Temperature Ambient Humidity Altitude 0 40 90 RH 3 000m 5 Medium Requirements Cooling medium allowed by the chiller includes purified water distilled water high pu...

Page 10: ...1 Please select the cable based on the max rated current indicated on the label of the chiller 2 Recommended reference standard for power cord diameter selection Rated current A 5 10 15 25 35 50 Wire...

Page 11: ...control mode It will self adjust controlling parameters according to room temperature for meeting equipment cooling requirements The new T 506E intelligent temperature controller is designed with con...

Page 12: ...ings After the power is on for 30 seconds press and hold and keys for 3 seconds until it displays rE The supplier parameter and user parameter will restore to factory value 3 seconds later it will ret...

Page 13: ...perature is 5 higher than the set water temperature and the alarm of over low water temperature will be on when water temperature is 10 lower than the set water temperature Users can easily adjust wat...

Page 14: ...rly disassemble the filter gauze for cleaning and use a compressed air gun to blow away the dust on the condenser about 1 week is suggested and the air filter must not be missing for a long time Displ...

Page 15: ...ending deformation Check water circulation pipe Ultrahigh water temperature alarm Blocked dust gauze bad thermolysis Disassemble and clean the dust gauze regularly Poor ventilation for air outlet and...

Page 16: ...TY JS 20319 003 16 Attachment Schematic CW 5300 flow sensor CW 5300 flow switch...

Page 17: ...TY JS 20319 003 17 CW 6000 flow sensor CW 6000 flow switch...

Page 18: ...TY JS 20319 003 18 CW 6100 6200 flow sensor CW 6100 6200 flow switch...

Page 19: ...TY JS 20319 003 19 CW 6260 flow sensor...

Reviews: