TY-JS-20319-003
6
air inlet and 1.5 meters around the air outlet. If the air inlet
and the air outlet are blocked, the cooling ability that the
equipment should have cannot be realized.
Before commissioning
a) Make sure that the water supply pipe of equipment is not
blocked;
b) It is necessary to check the water pipe and the water pump
to confirm that there is a proper amount of water entering the
water pump and exhaust it through the water pump exhaust
valve, otherwise it will cause damage to the water pump;
c) Confirm that the state of the equipment is normal and safe,
otherwise there may be injury and damage.
Gently move the
motor impeller if the
equipment isn’t used
for a long time
For equipment that has not been used for a long time, it may
be difficult to start the pump at the first start. Please gently
move the motor impeller before the equipment is powered on.
The equipment is
forbidden to be
trampled on
Please do not step on or sit on the equipment. Otherwise, it
may cause injury accidents such as falling or overturning
Clean the air filter
regularly
Clean the air filter at least once a week. If it is blocked, the
cooling ability will decrease and the power consumption will
increase, and the alarm will not work properly.
Equipment surface
cleaning
a) Please use cleaning agents that are non-corrosive to
metals and plastics;
b) Please keep the cleaning agent properly after cleaning to
prevent liquid leakage;
c) The container for storing the cleaning agent must be
sealed completely to avoid danger.
No air blowing at the
water outlet
A temp sensor is installed inside the water inlet, and it is
forbidden to blow air inside the device with an air gun.
Wear protective gloves
during maintenance,
inspection and cleaning
a) The sharp edges of the condenser fins may cut the skin;
b)The temperature of the internal compressor and refrigerant
piping is very high, and direct skin contact may cause burns.
Anti-freezing
a) When the ambient temperature is lower than 0
℃
and the
machine is shut down for a long time, it is necessary to drain
the liquid and blow the water away in the system with
compressed air, otherwise there is a danger of freezing and
cracking the components and pipelines.
b) When room temperature is lower than 0
℃
, it is
recommended to use antifreeze with a concentration of not
more than 30% containing ethylene glycol or propylene
glycol.
Summary of Contents for CW-5300
Page 1: ...TY JS 20319 003 1 CW 5300 6000 6100 6200 6260 Industrial Chiller User Manual...
Page 16: ...TY JS 20319 003 16 Attachment Schematic CW 5300 flow sensor CW 5300 flow switch...
Page 17: ...TY JS 20319 003 17 CW 6000 flow sensor CW 6000 flow switch...
Page 18: ...TY JS 20319 003 18 CW 6100 6200 flow sensor CW 6100 6200 flow switch...