Function Code 01: To read the current status of Digital Output with respect to
their device ID
•
Function Code 02: To read the current status of Digital Inputs with respect to
their device ID.
•
Function Code 03: To read the current status of Analog Inputs with respect to
their device ID.
•
Function Code 05: To operate DO with respect to their device ID.
4. Connection Details
Console:
Serial Interface
Interface:
RS-232
No. of Ports: 1 Port
Connector: 3 Pin Screw Type
PIN no.
PIN details
1
TX
2
RX
3
GND
RTU:
No. of Ports: 1 Port
Interface: RS- 485 (2-Wire)
Connector: 2 Pin Screw Type
PIN no.
PIN
details
1
D+/TX
2
D-/RX