SAMWONTECH
4th Edition of TEMI880 IM : Jan. 29. 2007 Page 105 / 119
4.4.4 Set Program Pattern
4.4.4.1 Program
▶ Program group is consisted of program pattern setting D-Registers.
▶ How to set a program pattern is :
Set one by one with changing number of segment on TEMI880.
▶ Program pattern setting D-Register
D-Reg.
Symbol
Value
Description
D1000
P_PTNO
1~120 Set program pattern number to Read or Write
D1001
DEST_PTNO
1~120 Set pattern number to be copied
0
Set to Read or Write on D1603~D1618
D1002
P_SEGNO
1~99 Set segment to Read or Write
1
INIT : D1000~D1004 value set '0'
2
READ : Reading value of D1000 and D1002
3
WRITE : Writing value of D1000 and D1002
4
PT COPY : Copy pattern D1000 to D1001
5
PT DEL : Delete pattern on D1000
6
SEG INSERT : Insert segment on D1000 and D1002
7
SEG DEL : Delete segment on D1000 and D1002
D1003
TRIGGER
8
ALL PT : Display pattern of D1000 to D1300 ...
0
FULL : Full memory for pattern or segment
1
DONE : Complete D1003(TRIGGER)’s job
2
PT EMPTY : Empty pattern
3
SEG EMPTY : Empty segment
4
PT RUN : PROG RUN Status
5
PARA ERROR : Setting error on D1000~D1003
D1004
ANSWER
6
PT USED : PROG RUN by pattern
D1010
TEMP_TSP
-
Temp. TSP(Target Set Point) to Read or Write
D1011
HUMI_TSP
-
Humi. TSP(Target Set Point) to Read or Write
D1012
SEG_TIME
-
Segment time to Read or Write
D1013
TS1
-
Time signal 1 to Read or Write
D1014
TS2
-
Time signal 2 to Read or Write
D1015
TS3
-
Time signal 3 to Read or Write
D1016
TS4
-
Time signal 4 to Read or Write