4th Edition of TEMI880 IM : Jan. 29. 2007 Page 103 / 119
4.4.2 FUNCTION
▶ Function group is consisted of D-Registers for operation
▶ PROGRAM running D-Register
D-Reg.
Symbol
Description
D0100
SET_PTNO
Set pattern number
D0121
WAITMD
Select using WAIT function ( 0 : OFF 1 : ON )
D0122
TEMP_WATE_ZONE
Set wait zone of Temp.
D0123
HUMI_WATE_ZONE
Set wait zone of Humi.
D0124
WAIT_TIME
Set wait time
▶ FIX running D-Register
D-Reg.
Symbol
Description
D0102
FIX_TEMP_SP
Set Temp. SP on FIX running
D0103
FIX_HUMI_SP
Set Humi. SP on FIX running
D0110
FIX_OPTM_SELL
Select using FIX OP TIME ( 0 : OFF 1 : ON )
D0111
FIX_OPTM_H
Set the hour for FIX OP TIME
D0112
FIX_OPTM _M
Set the minute for FIX OP TIME
▶ Operation D-Register
D-Reg.
Symbol
Status
Value
Description
RUN
1
PROG/FIX RUN
HOLD
2
HOLD ON/OFF
STEP
3
SEGMENT STEP
D0101
STATUS_MODE
STOP
4
PROG/FIX STOP
PROG
0
SET PROG MODE
D0104
OP_MODE
FIX
1
SET FIX MODE
STOP
0
SET STOP MODE
COLD
1
SET COLD MODE
D0105
PWR_MODE
HOT
2
SET HOT MODE
☞ For PROG RUN(or FIX RUN) through communication, TEMI880 must be STOP(PROG STOP/FIX STOP).
Ex) TEMI880 should be PROG STOP(D0104 = 0001, D0101 = 0004) for switching FIX RUN to PROG RUN.