Sym
Parameter
Setting Range
Unit
Initial
Remark
(note 1) : S.OPN(Sensor-Open)=BOUT(Burn-Out)
IN-T
Input Type
Refer to Table 1 Type of Input Sensor
ABS
TC.K1
All time
indicate
IN-U
Display Unit
℃ / °F
ABS
℃
T/C, RTD
IN.RH
Max. Value of
Measurement
Range
Within DEF. Range refer to Table 1
however, INRH > INRL
EU
1370
All time
indicate
IN.RL
Min. Value of
Measurement
Range
EU
-200
All time
indicate
IN.DP
Decimal Point
Position
0∼3
ABS
1
mV, V
IN.SH
Max Value
of Input Scale
Within -1999∼9999
however, INSH > INSL
The Decimal Point Position is relay on
the value of IN.DP
ABS
100.0
mV, V
IN.SL
Min Value
of Input Scale
0.0
mV, V
IN.FL
PV Filter
OFF, 1∼120
sec
OFF
All time
indicate
D.FL
Display Filter
OFF, 1∼120
sec
OFF
All time
indicate
BSL
BOUT SEL
(note1)
OFF, UP, DOWN
ABS
UP
(DCV=OFF)
All time
indicate
RSL
RJC SEL
ON, OFF
ABS
ON
T/C
BSP1
Reference
Bias Point1
EU(0.0∼100.0%),
RL BSP1 BSP2 BSP3 RH
EU
EU(100.0%)
All time
indicate
BSP2
Reference
Bias Point2
EU(0.0∼100.0%),
RL BSP1 BSP2 BSP3 RH
EU
EU(100.0%)
All time
indicate
BSP3
Reference
Bias Point3
EU(0.0∼100.0%),
RL BSP1 BSP2 BSP3 RH
EU
EU(100.0%)
All time
indicate
BS0
Bias Value for
RL Point
EUS(-100.0∼100.0%)
EUS
0
All time
indicate
BS1
Bias Value for
BSP1 Point
EUS(-100.0∼100.0%)
EUS
0
All time
indicate
BS2
Bias Value for
BSP2 Point
EUS(-100.0∼100.0%)
EUS
0
All time
indicate
BS3
Bias Value for
BSP3 Point
EUS(-100.0∼100.0%)
EUS
0
All time
indicate
BS4
Bias Value for
RH Point
EUS(-100.0∼100.0%)
EUS
0
All time
indicate