SAMWON ENG                                              SU-105 Instrument for Automatic Control of Temperature                                              Page 

4/4

 

③  Explanation of Period Timer operating process 

 

 
 
 

   
 
 
 

 

 
 
 
 

※  Period  Timer  will  operate  being  isolated  from  the  operation  of 
Thermometer.

 

 
 
 
 

※  Only for sendor TH, IC, HUM, A.. 

 

①When there

s an error in sensor during instrument

s operating, a damage 

could be minimized by leveled output value of prior output value, instead 
of shut-down.   

②This  PRESET  OUT  feature  is  available  only  in  the  condition  of  ON/OFF 

control,  On/OFF  time  should  be  within  1  second/18hours  in  average 
respectively. 

③Sampling  leveled  value  for  PRESET  OUT  is  from  the  latest  5  ON/OFF 
output value in the condition that output ON/OFF should be done 30 times 
lately. At every 30 output, its leveled value would be re-calculated. 

④How to PRESET OUT 

▶  Press    up  key  and    set  key  both  simultaneously  for  more  than  3 

seconds at current state. 

▶  up key and    set key both , until FIL appears. Release both key when   

FIL comes up on display. 

▶  set key several times to move to ot1. 
▶  Change the set value by using Up(up),Down(dn) key. 

   

FAC SET

 

 

ITEM 

VALUE 

EXPLANATION 

ot1 

onF 

Select ON/OFFcontrol. 

Po 

on 

Turn on PRESET OUT feature. 
(Default :OFF) 

Por 

1~100% 

Set the ratio of value to be leveled.   
(Default :90%) 

 

  ▶  set key for more than 3 seconds to memorize the value. 

▶Since  then,  this  feature  could  be  used  after  setting  controller  with 

ON/OFF control. 

④If 

” Pro”  

is  displayed  during  the  normal  operation  of  instrument, 

please  do  the  needed  arrangement,  as  it  says  that  there’ s  something 
wrong in sensor and PRESET OUT is running. After fixing sensor, PRESET 
OUT will stop itself and the instrument will work normally. 

 
 
 
 
 
 
 
 
 
 

 
 
 

Power Currency    AC100~220V (50/60Hz both)  ±10% 

Power 

consumption 

  About less than 5VA 

Input sensor 

  Thermo Couple : K/T(CA)   

allowed resist in wiring less than 100

Ω

 

Resistance Temperature Detector : PT100

Ω

   

allowed resist in wiring less than 5

Ω

 

Indication level 

  Thermo Couple :  ±0.5% +1digit of indicated value, 
  Resistance Temperature Detecto :±0.2% 

Variation(dIF)    0.1℃  ~ 25.0℃ 

Control Output 

Output from contact point of relay :   
AC250V 5A(resist load) 
Durability of contact point :   
higher than 300 thousands(rating load) 
 
 

Control operation     PI control or ON/OFFcontrol Selectable 

Set method 

  Digital by using Increase/decrease key 

Other feature 

  Correction of sensor input, delayed ON timer, selectable 
direction    Timer  for  Defreeze,  Correction  of  defected 
sensor 

Temperature 

around 

  0℃  ~ 50℃ 

Humidity around    Less than 85% RH 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

11. RESET of PRESET OUT

 

 

12. Product Specification

 

(주)삼원 ENG 의  다양한  전제품은  불량율  0.1%에  도전하고  있습니다.

 

 

 

HQ/factory : 703-4, HwamokDong, Kimhae-city, KyungNam 

         TEL:055-321-3030 (代)  FAX:055-321-3060 

Website: 

http://www.31eng.co.kr

    E-Mail : 

[email protected] 

 

         
           

       

  15min.  Off 

         

  5min.  On 

         

  15min.  Off 

         

  5min. 

On 

 

Period timer 
output at, 
Tim 

= Min 

odr = oFF 
ton = 5 
toF = 15 

 

 

주기

 

타이머

 

출력

 

  5sec. ON 

   

  15sec. OFF 

   

  5sec. ON 

     

  15sec. OFF 

 

Period Timer 
output at, 
Tim 

= SEC 

odr = on 
ton = 5 
toF = 15 

 

 

주기

 

타이머

 

출력

 