SAMWON ENG                                              SU-105 Instrument for Automatic Control of Temperature                                              Page 

3/4

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

①  Reset Aux. output as Alarm Output.   
  ▶  Aux. output is selectable for Alarm output and Period Timer output. 
      Therefore, it should be reset as Alarm output. 
      (It

s preset as Alarm output at manufacturer

s site.)   

  ▶To  reset  manufacturer

s  preset,  press  up  key  and  set  key  both 

simultaneously for more than 3 seconds at current state. 

▶  up  key  and    set  key  both  ,  until  FIL  appears.  Release  both  key  when   

FIL comes up on display. 

▶  set key several times to move to ot2. 

  ▶  When ot2 comes up, Up(up),Down(dn) key to change the preset value 
as below.

     

FAC 

SET   

 

ITEM 

VALUE 

EXPLANATION 

ot2 

AL 

Aux output is set as alarm output. 

  ▶  set key for 3~ seconds will memorize the changed value. 

②  How to set the temperature of Alarm output. 

▶  set  key  for  more  than  3  seconds  at  current  state.  Release  set  key 

when 

DiF or P

 comes up. 

▶  set key several times to move to SV2. 
▶  Change the set value by using Up(up),Down(dn), SET(set) key. 

   

Installer

s Reset 

 

 

Item 

Value 

Said to 

SV2 

Range of 

available temp. 

To set temperature of Alarm output. 

dF2 

0.1~25.0 

To set the value in the range of Alarm output 
OFF~ output ON. 

dt2 

0~300 sec. 

To set the delay time of Alarm output ON.   

ty2 

H / C 

To set    the value of Alarm output 
Heating(H/in right direction) and 
Cooling(C/in opposite direction). 

 

 

▶  set key for more than 3 seconds to memorize the value. 

Ex.1)    Assuming 20.0℃  of Alarm output temperature, dF2=5.0, dt2=10, ty2=H,   

Relay ON    : ON after 10 seconds waiting at 14.9℃   
Relay OFF : 20.0℃ 

Ex.2)    assuming 20.0℃  of Alarm output temperature, dF2=2.0, dt2=20, ty2=C, 

Relay ON    : ON after 20 seconds waiting at 22.1℃   
Relay OFF : 20.0℃ 

 

※  Alarm output will  operate  being  isolated from  the  operation of 

Thermometer. 

 
 
 
 

①  Set Aux. output to Period Timer output. 

▶  Aux.  output  is  selectable  for  Alarm  output  and  Period  Timer  output. 

Therefore, it should be reset as Period Timer output.. 

(It

s preset as Alarm output at manufacturer

s site.) 

▶  To  reset  manufacturer

s  preset,  press    up  key  and    set  key  both 

simultaneously for more than 3 seconds at current state. 

▶  up key and    set key both , until FIL appears. Release both key when   

FIL comes up on display. 

▶  set key several times to move to ot2. 
▶Change the set value by using Up(up),Down(dn) key. 

   

FAC. 

SET 

 

ITEM 

VALUE 

EXPLANATION 

ot2 

tIM 

Aux output is set as Period Timer output. 

 

▶  set key for 3~ seconds will memorize the changed value. 

②  How to set On/Off time of Period Timer output. 

▶  set  key  for  more  than  3  seconds  at  current  state.  Release  set  key 

when 

DiF or P

 comes up. 

▶  set key several times to move to tIM. 
▶  Change the set value by using Up(up),Down(dn), SET(set) key. 

   

Installer

SET

 

 

ITEM 

VALUE 

EXPLANATION 

tIM 

MIn / SEC 

Select value of Min/SEC. 

odr 

on / oFF 

Select value of initial output   

ton 

0 ~ 999 

Select output ON time value. 
* 0 

 continuous OFF state without ON 

time. 

toF 

0 ~ 999 

Select output OFF time value. 
* 0

 continuous ON state without OFF time.   

   

  ▶  set key for more than 3 seconds to memorize the value. 

 
 

 

8. PRESET at manufacturer

s site

 

Filter value(0~9): The shaking of displayed value could 
be minimized by leveling the input value for a certain 
time period. Its leveling time may slow down the 
reaction of input. (default value: 0) 

Up limit of preset (range of preset temperature) : will 
limit the preset temperature less than specified value. 
* With sensor A, limit will be decided by SCH value. 

up key and    set key both for more than 

3 seconds at current state. 

up key and    set key both , until 

FIL 

appears. Release both key when   

FIL comes up.

※  Repeat again, if dIF & 

P come up

 

Select  Main  output  PI(propotional  control)  and 
ON/OFF control OUT1 

공장

 

설정

 

항목

 

Set key for 3~ seconds will memorize all 

of value, and will display the current state. 

Set key to go back to start-up. 

Down  limit  of  preset(range  of  preset temperature)  : will 
limit the preset temperature higher than specified value. 
* With sensor A, limit will be decided by SCL value. 

Select out2 AL(alarm)/tIM(period timer)control

 

PRESET OUT select ON/OFF 

*Only for TH, IC, HUM, Asensor 
*Refer to 11. PRESET OUT 

PRESET OUT select ratio (1%~100%) 

*Only for TH, IC, HUM, Asensor 
*Refer to 11. PRESET OUT 

 

Up Limit of display(-999~+999):   

Limit  of  temperature  to  be  displayed  less  than 

specified value   

Up Limit of display(-999~+999):   

Limit  of  temperature  to  be  displayed  higher  than 

specified value . 

O

nl

fo

TH

IC

H

U

M

A

 s

e

ns

o

r

 

O

nl

fo

A

 s

e

ns

o

r

 

Appoint a decimal point(0~3):   

ex)    0 : 100    /    1 : 10.0    /    2 : 1.00 

Lock all of reset, except reset of temperature. 
ON:lock / OFF:release 
Change  to  Off  mode  in  advance  to  release  lock  of 
preset. 

 

 

 

9. RESET ALARM OUTPUT (AUX OUTPUT)

 

 

10. SET PERIOD TIMER

 