PAGE 47 of 79 VULCAIN OIL-FIRED HEATER
LAST UPDATED: JAN 22-2019 COPYRIGHT © SAMUEL JACKSON, INCORPORATED 2018 ALL RIGHTS RESERVED
Installation Stub-Ups for HO-7-Vulcain and HO-4-Vulcain
NO.
DESCRIPTION
ROUTING AND NOTES
1
BURNER 3-PHASE POWER
FROM POWER CENTER TO BURNER
CABINET.
3 – 10 GAUGE WIRES, 415 VAC OR
380 VAC, 6 HP, ¾ CONDUIT, 30 A
BREAKER. MOTOR STARTER AND
120 V CONTROL TRANSFORMER
ARE IN HEATER CABINET.
2
FAN INTERLOCK SIGNAL
FROM GIN CONSOLE OR MOTOR
CONTROL CENTER TO BURNER
CABINET. ONE ½” CONDUIT WITH
TWO 16 GA WIRES FOR INTERLOCK
SIGNAL (120 VAC, 240 VAC, OR 24
VDC)
3
THERMOCOUPLES
FROM BURNER CABINET TO:
AFTER MIX-POINT
THERMOCOUPLE
(MARKED BLUE)
ENTRANCE OF TOWER OR SECOND-
STAGE SKIMMER AIR OUTLET OF
COLLIDER DRYING SYSTEM.
(SEE
HEATER OPERATION
SECTION
FOR MORE INFORMATION ON
THERMOCOUPLE LOCATIONS)
HIGH LIMIT
BEFORE MIX-POINT
THERMOCOUPLE
(MARKED RED)
½” CONDUIT WITH SHIELDED
2 CONDUCTOR, 18 GA CABLE. *
DO NOT RUN WITH AC VOLTAGE
WIRES. OKAY TO RUN WITH
OTHER THERMOCOUPLE OR DC
VOLTAGE SENSOR WIRES.