PAGE 31 of 79 VULCAIN OIL-FIRED HEATER
LAST UPDATED: JAN 22-2019 COPYRIGHT © SAMUEL JACKSON, INCORPORATED 2018 ALL RIGHTS RESERVED
Test Program
For software versions 1.0 and later
PRELIMINARY:
To test a new installation, first check that all necessary connections for electrical and fuel
are made. Standard 3-phase electrical power supplies are 415 VAC/50 HZ or 380
VAC/50HZ.
Turn on the electrical power to the cabinet, but leave the circuit breaker (CB) off. Check
that power to terminals 1 and 2 on the electrical panel is between 110 and 125 VAC.
Check that the thermocouples are connected and hooked to the correct terminals on the
electrical panel and then turn on the circuit breaker (CB). If a temperature shows 777 on
the color touch panel, then the thermocouple is not connected. A good test to check that
thermocouple is connected to correct panel terminals is to disconnect one of the wires at
the thermocouple. The temperature displayed for that thermocouple (before or after
mixpoint) should be 777.
Oil Burner Head and Purge Line
Oil cock at back of
burner head
(Open to Purge)