1 ) Is the voltage of the power corre c t ?
The input voltage shall be 198-264VAC.
The airconditioner may not operate properly if the voltage is out of this range.
2 ) Is the link cable linking the indoor unit and the outdoor unit linked pro p e r l y ?
The indoor unit and the outdoor unit shall be linked by 5 cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the airconditioner may not operate pro p e r l y.
3 ) When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the
malfunction of the airc o n d i t i o n e r.
4 ) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details
on the display panel.
Samsung Electronics
5-1
5. Troubleshooting
5-1 Items to be checked first
NO
Operation of air conditioner
1
The COOL operation indication LED (Green) blinks when a
power plug of the indoor unit is plugged in for the first time.
2
In a COOL operation mode, the compressor does not
operate at a room temperature higher than the setting
temperature that the IN DOOR FAN should operate.
In a HEAT operation mode, the compressor does not
operate at a room temperature lower than the setting
temperature that indoor fan should
operate.
3
Fan speed setting is not allowed in AUTO or DRY mode.
4
Compressor stops operation intermittently in DRY mode.
5
Compressor of the outdoor unit is operating although it is
turned off in a HEAT mode.
6
Timer LED only of the indoor unit lights up and the
air conditioner does not operate.
7
The compressor and indoor fan stop intermittently in HEAT
mode.
8
Indoor fan and outdoor fan stop operation intermittently in
a HEAT mode.
9
The compressor stops intermittently in a COOL mode or DRY
mode, and fan speed of the indoor unit decreases.
It indicates power is on. The LED stops blinking if the operation
ON/OFF button on the remote control unit is pushed.
In happens after a delay of 3 minutes when the compressor is reoper-
ated. The same phenomenon occurs when a power is on.
As a phenomenon that the compressor is reoperated after a delay of
3 minutes, the indoor fan is adjusted automatically with reference
to a temperature of the air blew
The speed of the indoor fan is set to LL in DRY mode.
Fan speed is 5 steps is selected automatically in AUTO mode.
Compressor operation is controlled automatically in DRY mode
depending on the room temperature and humidity.
When the unit is turned off while de-ice is activated, the compressor
continues operation for up to 9 minutes (maximum) until the deice is
completed.
Timer is being activated and the unit is in ready mode.
The unit operates normally if the timer operation is cancelled.
The compressor and indoor fan stop intermittently if room temperature
exceeds a setting temperature in order to protect the compressor from
overheated air in a HEAT mode.
The compressor operates in a reverse cycle to remove exterior ice in a
HEAT mode, and indoor fan and outdoor fan do not operate intermit-
tently for within 20% of the total heater operation
The compressor stops intermittently or the fan speed of the indoor unit
decreases to prevent inside/outside air frozen depending on the
inside/outside air temperature.
Explanation
NO
Display
1
Operating LED blinking (1Hz)
2
TIMER LED blinking (1Hz)
3
O P E R ATING and TIMER LED blinking (1Hz)
4
FAN LEA blinking (1Hz)
Restore from power failure (input initial power)
Indoor unit Room sensor Error (open or short)
Indoor unit heat exchanger temperature sensor Error (open or short)
Indoor fan malfunctioning (for spead is Below 38Orpm)
Self Diagnosis
Summary of Contents for US07A1VE
Page 2: ... Samsung Electronics Co Ltd FEB 1997 Printed in Korea Code No DB81 10122A 1 ...
Page 4: ...1 2 Samsung Electronics MEMO ...
Page 27: ...Samsung Electronics 3 14 MEMO ...
Page 42: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit ...
Page 44: ...Samsung Electronics 6 3 6 2 Outdoor Unit 24 1 24 25 25 2 25 1 25 3 25 4 25 5 18 18 1 19 ...
Page 48: ...6 7 Samsung Electronics MEMO ...
Page 50: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 a Main PCB 7000Btu DB93 10483A ...
Page 52: ...Samsung Electronics 8 3 8 1 b Main PCB 9000 12000Btu 12000BUT DB93 10471A 9000BUT DB93 10485A ...
Page 55: ...Samsung Electronics 9 1 9 Wiring Diagrams 9 1 Indoor Unit ...
Page 57: ...Samsung Electronics MEMO ...
Page 58: ...Samsung Electronics MEMO ...
Page 59: ...10 1 10 Schematic Diagrams 10 1 Indoor Unit Samsung Electronics ...
Page 60: ...Samsung Electronics 10 2 10 2 Remote Control ...