20mm
Indoor Unit
Ceiling
Gauge of
Dimensions
17mm
ENGLISH
Indoor Unit Installation
It is recommended to install the refnet joint before installing the indoor unit.
1
Place the pattern sheet on the ceiling at the spot where you want to install
the indoor unit.
Note
Since the diagram is made of paper, it may shrink or stretch
slightly due to temperature or humidity. For this reason,
before drilling the holes maintain the correct dimensions between
the markings; refer to page 6.
2
Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in figure.
3
Install the suspension bolts depending on the ceiling type.
IM
PORTANT
Ensure that the ceiling is strong enough to support
the weight of the indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
If the length of suspension bolt is more than 1.5m,
it is required to prevent vibration.
4
Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
IM
PORTANT
You must install the suspension bolts more than four
when installing the indoor unit.
5
Hang the indoor unit to the suspension bolts between two nuts.
Note
Piping must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay the
piping into position for connection to the unit before placing the unit
inside the ceiling.
6
Screw the nuts to suspend the unit. Cut a pad stopper and place it on the
bracket at this time.
7
Adjust the unit to the appropriate position considering the installation area for the
front panel.
7-1 Place the pattern sheet on the indoor unit.
7-2 Adjust a space between the ceiling and the indoor unit by using the gauge
of dimensions.
7-3 Fix the indoor unit securely after adjusting level of the unit by using a leveler.
7-4 Remove the pattern sheet, connect the other cables and install the front panel.
Concrete
Suspension bolt(M8)-field supply
Hole in anchor
Hole in plug
Insert
Ceiling support
Pad stopper
Bracket