Performing Leak Test & Insulation
ENGLISH
Insulation
cover pipe
Be sure to overlap
the insulation
Indoor Unit
Insulation pipe
CAUTION
Must fit tightly against body
without any gap.
No gap
NBR(T13.0 or thicker)
To check for gas leaks on the indoor unit, check the connection part of each
refrigerant pipe by using a leak detector.
Leak Test
Insulation
Once you have checked that there are no leaks in the system,
you can insulate the piping and hose.
1
To avoid condensation problems, place T13.0 or thicker Acrylonitrile
Butadiene Rubber around each refrigerant pipe.
Note
Always make the seam of pipes face upwards.
2
Wind insulating tape around the pipes and drain hose.
3
Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit.